Communication profiles 79
2
OFF3_CONTROL
1
Continue operation (OFF3
inactive).
0
Emergency stop, stop within the
time defined by the drive
parameter.
Proceed to
OFF3 ACTIVE
;
proceed to
SWITCH-ON
INHIBITED
.
Warning:
Ensure that the motor
and driven machine can be
stopped using this stop mode.
3
INHIBIT_OPERATION
1
Proceed to
OPERATION
ENABLED
.
Note:
The Run enable
signal
must be active; see the drive
manuals. If the drive is set to
receive the Run enable signal
from the fieldbus, this bit
activates the signal.
0
Inhibit operation.
Proceed to
OPERATION
INHIBITED
.
4
RAMP_OUT_ZERO
1
Normal operation.
Proceed to
RAMP FUNCTION
GENERATOR: OUTPUT
ENABLED
.
0
Force the Ramp Function
Generator output to go to zero.
The drive ramps the speed down
to zero and stops (keeping the
current and DC voltage limits in
force).
5
RAMP_HOLD
1
Enable the ramp function.
Proceed to
RAMP FUNCTION
GENERATOR: ACCELERATOR
ENABLED
.
0
Halt ramping (Ramp Function
Generator output held).
Bit
Name
Value Description
Содержание FECA-01 EtherCAT
Страница 1: ...Options for ABB drives converters and inverters User s manual FECA 01 EtherCAT adapter module ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 14: ...14 Safety instructions ...
Страница 28: ...28 Mechanical installation ...
Страница 32: ...32 Electrical installation ...
Страница 63: ...Start up 63 ...
Страница 66: ...66 Start up ...
Страница 86: ...86 Communication profiles ...