Start-up 43
1608 START ENABLE 1
COMM
Selects the fieldbus interface as
the source for the inverted Start
Enable signal.
1609 START ENABLE 2
COMM
Selects the fieldbus interface as
the source for the Start Enable 2
signal.
2201 ACC/DEC 1/2 SEL
COMM
Selects the fieldbus interface as
the source for the ramp pair 1/2
selection.
2209 RAMP INPUT 0
COMM
Selects the fieldbus interface as
the source for forcing the ramp
input to zero.
9904 MOTOR CTRL
MODE
VECTOR:SPEED
VECTOR:TORQ
SCALAR:FREQ
Selects the motor control mode.
Note:
The CiA 402 operation
modes available depend on this
setting.
• When VECTOR:TORQ has
been selected, operation
modes vl, tq and cst are
available.
• When VECTOR:SPEED or
SCALAR:FREQ has been
selected, only the vl mode is
available.
Drive parameter
Setting for ACS355
drives
Description