42 Start-up
Parameter setting examples – ACS355
The ACS355 parameters and mandatory parameter settings for
the EtherCAT fieldbus communication with the CiA 402 profile are
listed in the following table.
Note:
All other ACS355 parameters not mentioned in the table
below are assumed to be at their default values.
Drive parameter
Setting for ACS355
drives
Description
9802 COMM PROT SEL
EXT FBA
Activates the communication
(fieldbus) module.
5101 FBA TYPE
EtherCAT
Displays the type of the fieldbus
adapter module.
5102 FB PAR 2
(PROFILE)
0
(= CiA 402)
Selects the CiA 402 profile.
5127 FBA PAR
REFRESH
REFRESH
Validates the FECA-01
configuration parameter
settings.
1001 EXT1
COMMANDS
COMM
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 1.
1002 EXT2
COMMANDS
COMM
Selects the fieldbus interface as
the source of the start and stop
commands for external control
location 2.
1102 EXT1/EXT2 SEL
COMM
Enables external control location
1/2 selection through the
fieldbus.
1103 REF1 SELECT
COMM
Selects the fieldbus reference 1
as the source for speed
reference.
1106 REF2 SELECT
COMM
Selects the fieldbus reference 2
as the source for torque
reference.
1601 RUN ENABLE
COMM
Selects the fieldbus interface as
the source for the inverted Run
enable signal (Run disable).
1604 FAULT RESET
SEL
COMM
Selects the fieldbus interface as
the source for the fault reset
signal.
Содержание FECA-01 EtherCAT
Страница 1: ...Options for ABB drives converters and inverters User s manual FECA 01 EtherCAT adapter module ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 14: ...14 Safety instructions ...
Страница 28: ...28 Mechanical installation ...
Страница 32: ...32 Electrical installation ...
Страница 63: ...Start up 63 ...
Страница 66: ...66 Start up ...
Страница 86: ...86 Communication profiles ...