46 Start-up
10.08 FAULT RESET
SEL
P.FBA MAIN CW.8
Selects the fieldbus interface as
the source for the fault reset
signal.
24.01 SPEED REF1 SEL FBA REF1
Selects the fieldbus reference 1
as the source for speed
reference 1.
32.01 TORQ REF1 SEL
FBA REF1
Selects the fieldbus reference 1
as the source for torque
reference 1.
34.01 EXT1/EXT2 SEL
C.False
Selects that the external control
location is always EXT1.
34.02 EXT1 MODE
1/2SEL
C.False
Selects the source for the
default drive control mode
selection.
34.03 EXT1 CTRL
MODE1
Speed
Torque
Position
Synchron
Selects the default (power up)
drive control mode.
3)
For more information on using
the position control mode, see
ACSM1 motion control program
firmware manual
(3AFE68848270 [English]).
57.09 KERNEL SYNC
MODE
FBSync
See section
on page
.
60.02 POS AXIS MODE
Linear
Rollover
Selects whether to have
continuous position data range
or position data range with one
revolution wrap-around.
4)
60.09 POS
RESOLUTION
10…24
Selects the internal resolution of
the position data between the
module and the drive, not at the
master.
5)
60.05 POS UNIT
Revolution
Mandatory setting
60.10 POS SPEED UNIT u/s
Mandatory setting
62.01 HOMING
METHOD
CAN Method 1 …
CAN Method35
Selects the homing method. The
homing method needs to be
selected if one intends to use
homing.
For more information on the
homing methods, see
ACSM1
motion control program firmware
manual
(3AFE68848270
[English]).
Drive parameter
Setting for ACSM1
drives
Description
Содержание FECA-01 EtherCAT
Страница 1: ...Options for ABB drives converters and inverters User s manual FECA 01 EtherCAT adapter module ...
Страница 4: ......
Страница 10: ...10 Table of contents ...
Страница 14: ...14 Safety instructions ...
Страница 28: ...28 Mechanical installation ...
Страница 32: ...32 Electrical installation ...
Страница 63: ...Start up 63 ...
Страница 66: ...66 Start up ...
Страница 86: ...86 Communication profiles ...