Appendix A – CoE Object Dictionary 119
1C33
0 Input sync man-
ager parameter
U8
R
Sync manager 3 syn-
chronization settings
-
1 Synchroniza-
tion type
U16
RW
0x00 = Free run (de-
fault)
0x01 = SM sync, SM3
event
0x22 = SM sync, SM2
event
0x02 = DC Sync0
FBA
4 Synchroniza-
tion types sup-
ported
U16
R
Drive dependent. Bits:
• 4…2: 000 = No DC,
001 = DC Sync0
• 1: SM sync support-
ed
• 0: Free run support-
ed
-
5 Minimum cycle
time
U32
R
See subindex 5 of in-
dex 1C32.
500 000.
-
6 Calc and copy
time
U32
R
Delay between the
time of input process
data sampling and the
time when the data is
available for the master
(ns)
88 000.
-
C Cycle time too
small
U16
R
See subindex C of in-
dex 1C32.
-
Index SI Name
Type
Ac-
cess
Information
NVS