![ABB FECA-01 EtherCAT Скачать руководство пользователя страница 100](http://html.mh-extra.com/html/abb/feca-01-ethercat/feca-01-ethercat_user-manual_2715100.webp)
100 Diagnostics
Name
Color
Function
LINK/ACT
(IN/X1)
Off
No link on port 0
Green
Link OK on port 0, no activity
Green flickering
Activity on port 0
LINK/ACT
(OUT/X2)
Off
No link on port 1
Green
Link OK on port 1, no activity
Green flickering
Activity on port 1
STATUS
Off
INIT state
Green blinking
PREOP state
Green single flash
SAFEOP state
Green
OP state
Red blinking
State change requested by the
master is impossible because of a
local error
Red single flash
State changed autonomously by a
slave because of a local error
Red double flash
Process data watchdog time-out
Green flickering
Module is booting up.
At the first start-up this may take
approximately 1 minute.