114 Option
Set MAU PLC parameters.
If more than one motors are to be sync to mains, marshalling PLC (optional) is used.
It
provides parameters, events and IO signals interface to user
.
Web visualization is used as
interface of marshalling PLC.
Requirements for commissioning PC
1. In order to access PLC, user’s computer has to meet below conditions.
•
Operating system: Windows NT/2000/XP/7/10, Windows CE, Linux, RTE.
•
A Web-Browser (IE-Explorer or Netscape)
•
JavaScript is installed on PC. The Java.exe installation could be downloaded from the
official website
https://www.java.com/en/
2. IP address and Subnet mask setting
•
Connect Marshalling PLC and PC with ethernet cable.
•
Set Marshalling PLC (optional) and Panel (optional) as below table.
•
set the PC IP address in the same segment, e.g. 192.168.0.13, and with same Subnet
mask.
Drive parameter
Setting
Description
16.19 DIO3 function
Output
Select DIO3 as output
16.21 DIO3 output
source
P 85.2.14
Inductor bypass contactor close command signal is from
SBU function SW bit 14
16.24 DIO4 function
Output
Select the DIO4 as the output
16.26 DIO4 output
source
P 85.2.15
Inductor bypass contactor open command signal is from
SBU function SW bit 15
85.21 Bypass
contactor control
Enabled
Enable inductor bypass contactor control
85.22 Contactor
control signal
Pulse signal
Inductor bypass contact is using pulse signal for control
Marshalling PLC
Panel (CP610)
IP address
192.168.0.10
192.168.0.11
Subnet mask
255.255.255.0
255.255.255.0
Содержание ACS580MV
Страница 1: ... ABB INDUSTRIAL DRIVES ACS580MV Commissioning Manual 200kW to 6300 kW 3 3kV to 11 kV ...
Страница 4: ......
Страница 8: ...8 ...
Страница 43: ...Standard Commissioning Process 43 Press the button Load SW and wait till update is finished ...
Страница 45: ...Standard Commissioning Process 45 In this step should select Lab Tools Standalone Installation ...
Страница 60: ...60 Standard Commissioning Process Complete the installation press Finish ...
Страница 83: ...Standard Commissioning Process 83 ...
Страница 96: ...96 Standard Commissioning Process ...
Страница 121: ...Option 121 IO signals ...
Страница 122: ...122 Option Panel control interface System fault ...
Страница 140: ...140 Option ...
Страница 148: ...148 Preventive Maintenance ...