52 Standard Commissioning Process
Note:
If the error information like below, please new a folder named temp in drive C
.
•
Waiting nearly 25 seconds, programming successfully finished.
Press any key to exit.
•
Turn off the control power.
•
Remove the XILINX platform cable USB II.
Loading the IO controller (AC500eco) software
•
Save the following files and folders to the SD card (MC502) root folder. Files can be
found in the loading package (folder \04_IOController SW).
Note:
Only MC502 SD card can be used. This is not the same SD card which is plugged
into the BCU.
•
Switch off the control power
.
•
Install SD card adapter (MC503) into CPU PM55X.
•
Inset SD memory card (MC502) into adapter MC503.