132 Option
1.
General configuration of Master
2.
General configuration of Torque Follower
ACS580MV Master Parameter Settings
Parameter
Name
Setting
Description
19.11
Ext1/Ext2 selection
Ext1
19.12
Ext1 control mode
Speed
60.1
M/F comm port
RDCO CH2
Channel of DDCS M/F
60.2
M/F node address
0 or 1
60.3
M/F mode
DDCS master
60.9
M/F comm loss function
Fault
Master’s action when comm loss
happens
60.10
M/F ref1 type
Speed
Ref1 is used for speed control
60.11
M/F ref2 type
Torque
Ref2 is used for torque control
60.17
Follower fault action
Fault
Master’s action when Followers have
fault
60.14
Follower nodes
User dependent
(optional) Master selects the Followers
which need to be surveilled, and the
related Follower node data sel need to
be set (P62.4~10)
61.1
M/F data 1 selection
CW 16bit
Master selects the data which transmit to
the Followers. The data value shown as
P61.25~27
61.2
M/F data 2 selection
Other P23.2
61.3
M/F data 3 selection
Torque reference
used
62.4
Follower node 2 data 1 sel
Follower SW
(Optional)
Master selects the data which receive
from the Followers. The data value
shown as P62.28~36
62.5
Follower node 2 data 2 sel
User dependent
62.6
Follower node 2 data 3 sel
62.7
Follower node 3 data 1 sel
Follower SW
62.8
Follower node 3 data 2 sel
User dependent
62.9
Follower node 3 data 3 sel
62.10
Follower node 4 data 1 sel
Follower SW
62.11
Follower node 4 data 2 sel
User dependent
62.12
Follower node 4 data 3 sel
25.8
Drooping rate
User dependent
Defines the droop rate (in percent of the
motor nominal speed)
ACS580MV Follower Parameter Settings — Torque Follower
Parameter
Name
Setting
Description
19.11
Ext1/Ext2 selection
Ext2
19.14
Ext2 control mode
Torque
Содержание ACS580MV
Страница 1: ... ABB INDUSTRIAL DRIVES ACS580MV Commissioning Manual 200kW to 6300 kW 3 3kV to 11 kV ...
Страница 4: ......
Страница 8: ...8 ...
Страница 43: ...Standard Commissioning Process 43 Press the button Load SW and wait till update is finished ...
Страница 45: ...Standard Commissioning Process 45 In this step should select Lab Tools Standalone Installation ...
Страница 60: ...60 Standard Commissioning Process Complete the installation press Finish ...
Страница 83: ...Standard Commissioning Process 83 ...
Страница 96: ...96 Standard Commissioning Process ...
Страница 121: ...Option 121 IO signals ...
Страница 122: ...122 Option Panel control interface System fault ...
Страница 140: ...140 Option ...
Страница 148: ...148 Preventive Maintenance ...