Normal measuring mode LMG450
92
The following examples exit if you have the wiring ‘A:1+2 B:3+4’ and the Aron field is
switched on in the measuring menu.
Example: Chn2 (U23,I2) A:2
This is the measuring channel 2. It should be connected to U23 and I2 of your circuit. It
belongs to group A and has the display channel number 2.
Example: Link34 (U12,I3) B:6
This is a linked channel, which is calculated from values of channel 1 and 2. The displayed
values represent U12 and I3 of your circuit. It belongs to group B and has the display channel
number 6.
Example: Sum(1-2) A:13
This is the sum channel which is calculated over the display channels 1 to 2. It belongs to
group A and has the display channel number 13.
For further information please refer also 2.4, ‘The group concept’ and 2.5, ‘Linked values’.
5.4.1 Default
With
Default you see the most important values of the instrument. For the handling please see
the general description in chapter 5.4, ‘Display of values’.