EDA-Z5008, Z5020 & Z5100 – Technical Manual
ZPControlTechMan_r105
_____________________________________________________________________________________________________
13
④
Fault LEDs
Common Fault
Device or panel has a fault. See main display for details.
System Fault
Fault that affects system performance. See main display for details.
Sounder Flt/Disable
If the LED is flashing, there is a fault with one or more sounders. If the
LED is solid, the sounders have been disabled.
Routing Flt/Disable
If the LED is flashing, there is a fault with the fire routing relay. If the LED
is solid, the fire routing relay has been disabled.
Routing Active
Illuminated when the fire routing relay has been activated
⑤
Keys
Menu/Info
Press to initiate the menu system. If held down for longer than 2 seconds,
the LEDs will follow a test sequence (lamp test).
Function
This button is disabled by default, though it can be programmed to do a
number of functions. See 6.8 – User Options.
Cancel
Used to return to the main screen from a menu or to return to the menu
from a programming screen.
Enter
This is used to accept information programmed into the panel.
Re-sound Alarm
Following an alarm condition that has been silenced, this button will re-
sound the alarm.
Silence Alarm
If the panel is in a fire condition this will silence the sounders.
Silence Buzzer
Silences the panel buzzer for all currently displayed faults or alarms.
Reset
Resets the panel from an alarm or fault condition. Note that the system
must be silenced before it can be reset from a fire condition.
⑥
Navigation Keys
Use to navigate through the menu structure and programming/status screens. In a multiple
fault or alarm condition, the up and down arrow keys allow the user to scroll through all the
current events. The display will also scroll automatically every 4 seconds.
The navigation keys are numbered 1 to 4. This is to allow the user to enter a 4 digit access code
when prompted.