EDA-Z5008, Z5020 & Z5100 – Technical Manual
ZPControlTechMan_r105
_____________________________________________________________________________________________________
26
6.18 - Panel Text – commissioning users
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>3.Panel Text
This menu allows the user to set a name and/or location for the panel. This will be displayed on the
system normal screen. Enter text using the panel keys or by connecting a standard USB keyboard.
6.19 - SIM Operations – commissioning users
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>4.SIM Operations
The memory card should be fitted at all times. It stores a complete
set of the system settings including text and options. If
‘Load from
SIM’
is selected, all panel settings will be overwritten with the
settings stored on the memory card. This can be useful when
replacing a panel.
‘Save to SIM’
will save all the current panel
settings to the memory card.
6.20 - Device Assignment – commissioning users
1.Main Menu>>1.Setup>>4.System Setup>>4.Device Assignment
Devices on the system are assigned to communicate with the
antenna on the main panel by default, so if any radio booster
panels or additional antennas have been added it is important that
each device is reassigned to the panel or wired antenna with the
best signal strength. The
‘1-Auto Assign’
option will automatically
assign each device to the panel or antenna it receives the strongest
signal from. This can be done for one device or for all devices at
once. Be sure to clear the verify table first and wait 15 minutes
before running the auto assignment. The process will take 20
seconds per device.
‘2-Assign Device’
will allow the user to manually assign any device on the system to any panel or
antenna. Devices should be deassigned before assigning to an antenna.
‘3-Deassign Device’
will
deassign the selected device from a specific antenna.
‘4-Deassign All’
will deassign all devices from a
specific antenna.
6.21 - Panel Assignment – commissioning users
1.Main Menu>>1.Setup>>4.System Setup>>4.Device Assignment>>5.Panel Assignment
When a control panel has multiple antennas connected (via the SMA connector and the RS-485
connectors), any repeater panels will be assigned to communicate with the control panel stub antenna
by default.
‘1-Assign Panel’
allows the user to assign any repeater panel to a particular antenna
connected to the main panel. Selecting
‘2-Deassign Panel’
will remove a specified link.
When a repeater panel has multiple antennas connected, any other panels will be assigned to
communicate with the repeater panel stub antenna by default. By attaching the control panel display
board to the repeater panel and using the options in the panel assignment menu, any other panel can
be assigned to a particular antenna connected to the repeater panel.
Device 001
Polling
P1A1:+20 P1A2:+14
Ensure all devices
are fitted in bases
ENTER to continue
Save to SIM?
ENTER to continue