EDA-Z5008, Z5020 & Z5100 – Technical Manual
ZPControlTechMan_r105
_____________________________________________________________________________________________________
24
6.11 - HMO Zones – commissioning users
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>1.Panel Options>>4.HMO Zones
Use the
↑
and
↓
keys to select the zone, and press
Enter
to
change the zone type. Zones can be designated as either common
zones or dwelling zones. See 6.7 – HMO System for more
information. Press
→
when you have finished making changes,
then press
Enter
to save.
6.12 - HMO Options – commissioning users
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>1.Panel Options>>5.HMO Options
The menu allows the user to change the settings the HMO system was setup with.
Alert Tone
This tone will operate in the dwelling where the activation originated.
Alert Relay
This relay can be set to on, off or pulse when the alert tone is active.
Evac Tone
Tone to be sounded if a dwelling device has not been silenced within the react
time, or if a device in a common zone is triggered.
Evac Relay
This relay can be set to on, off or pulse when the Evac tone is being sounded.
React Time
If an alert is not silenced within this time period, the system will trigger an
evacuation.
Ventilate Time
After the panel is silenced the panel will ignore all other fire signals in that zone
until this timeout expires. This is to give the occupant time to ventilate the
dwelling without causing another alert.
Alert Period
If the alert limit is reached within this time period, the whole building will be
evacuated.
Alert Limit
The number of activations allowed during the alert period. Once reached, the
panel will evacuate the whole building.
6.13 - User Tones – commissioning users
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>1.Panel Options>>6.User Tones
This menu allows the user to create 4 custom alarm tones. User tones can be made from adding any of
four basic tones; HIGH, LOW, WARBLE and SWEPT.
6.14 - User Relays – commissioning users
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>1.Panel Options>>7.User Relays
This menu allows the user to create 4 custom relay profiles. In a profile each of the panel’s 4 relays can
be set as OFF, 1 SEC ON/OFF, 1 SEC ON 2 SEC OFF or ON.
Zone 001↕
Dwelling Zone
ENTER for Zone Type