EDA-Z5008, Z5020 & Z5100 – Technical Manual
ZPControlTechMan_r105
_____________________________________________________________________________________________________
33
7.0 - Disable/Enable
Disable a Zone – all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>1.Zone
If a zone is disabled the system will not display any fire or fault
events for devices located in that zone. This includes any call point
activations. Select the zone number to be disabled and press the
→
key. Select the timeout period followed by the
→
key. All access
levels can disable a zone for a period of 1 to 96 hours. A
commissioning user can disable a zone indefinitely by selecting a
time of ‘00’ hours. Press
Enter
to save the change. ‘Zone XXX
disabled’ will be displayed on screen and the LED marked
‘Disablements’ will now be illuminated on the panel. After the
timeout period has elapsed, the isolated zone(s) will automatically
be re-enabled.
Disable a Device – all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>2.Device
If a device is disabled the system will not display any fire or fault
events for that device. Using the
↑
or
↓
keys select the device
number to be disabled and press the
→
key. Select the timeout
period followed by the
→
key. All access levels can disable a zone
for a period of 1 to 96 hours. A commissioning user can disable a
zone indefinitely by selecting a time of ‘00’ hours. Press
Enter
to
save the change. ‘Device XXX disabled’ will be displayed on screen
and the LED marked ‘Disablements’ will now be illuminated on the
panel. After the timeout period has elapsed, the isolated device(s)
will automatically be re-enabled. Press
Cancel
to exit or
Enter
to
disable more devices. If all devices in a zone are disabled, the zone
is also disabled. If a sounder detector is disabled, only the detector component ceases to function. The
device will still sound in an alarm. If a square sounder is disabled, only the reporting of faults from the
device is disabled – the sounder will still sound in an alarm.
Disable Panel Inputs – all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>3.Panel Input
The two monitored inputs can be disabled for a period of time specified by the user, dependent on
their access level. All access levels can disable an input for a period of 1 to 96 hours. A commissioning
user can disable an input indefinitely by selecting a time of ‘00’ hours. Press
Enter
to save the change
‘Input XXX disabled’ will be displayed on screen and the LED marked ‘Disablements’ will now be
illuminated on the panel. The system will ignore any fire or fault event from that input within that time.
After the timeout period has elapsed any disabled inputs will automatically be enabled again.
Select Zone 001↕
Use ← → keys
Press ENTER to
Disable Zone 001
Select Device 001↕
SMOKE DET
Use ← → keys
Press ENTER to
Disable Device 001