14.0 – Delays
It is possible to set two delays for each device or input - see 6.32 – Edit Device Options. A combined
delay period of up to 600 seconds can be applied for delay1 and delay2 (e.g. 300 seconds each).
The system will ignore any programmed delays until they are activated at Access Level 2. To turn delays
on or off, the function key may be used, which will require an access code to be entered. Alternatively
delays can be activated with a panel input. Panel input activation must be restricted by, for example,
using a keyswitch. This function must be restricted for use by the designated person authorised to
operate the panel. When turned on, the ‘Delays Active’ LED will illuminate.
At least 1 callpoint must be on the system so that a delay can be overridden. It is not possible to set a
delay for a callpoint.
14.1 – Set Function Key as a Delay Toggle Switch
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>1.Panel Options>>1.User Options
Press the
→
key until the function key screen is displayed. Use the
↑
and
↓
keys to select delay toggle as shown. Press the
→
key until
‘Press Enter to save’ is displayed and press
Enter
. Now when the
Function key is pressed and a correct access code is entered, the
Delays Active LED will illuminate.
14.2 – Set up a Keyswitch as a Delay Toggle Switch
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>2.Panel Inputs>>3.Keyswitch Options
Press the
→
key until the key function screen is displayed. Use the
↑
and
↓
keys to select delay toggle as shown. Press the
→
key until
‘Press Enter to save’ is displayed and press
Enter
. When the key is
turned, the Delays Active LED will illuminate.
14.3 – Double Knock
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>1.Panel Options>>1.User Options
This function is typically used in conjunction with delays. Upon activation of a second device the system
will use settings to signal a full evacuation. The double knock can be set to function either by a second
device the same zone, or on a system wide basis.
Func Key 3↕
Delay Toggle
Use ← → keys
Key Function 6↕
Delay Toggle
Use ← → keys