EDA-Z5008, Z5020 & Z5100 – Technical Manual
ZPControlTechMan_r105
_____________________________________________________________________________________________________
30
6.29 - Adding a Device – commissioning users
1.Main Menu>>1.Setup>>5.Device Setup>>2.Add Device
Additional devices can be added to the system at any time. The device needs to be put into
programming mode in order to add it to the system. First remove the device from its base or backplate.
1.
If a smoke, heat detector or combined sounder is being programmed; hold both the reset
button and the unit removal button down while you place the jumper link to the ON position.
2.
If a beacon, sounder, callpoint, transmitter or I/O unit is being programmed; hold down the unit
removal button while holding a magnet over the reed switch and move the jumper link to the
ON position. Some newer devices are equipped with a ‘log on’ button and do not require a
magnet to program. Simply hold the button while placing the jumper link to the ON position.
Continue to hold the button(s) for approximately 5 seconds until a
confirmation of 3 beeps from the device is heard. The LED on the
device will now flash green. Press
Enter
to scan for the device.
Once the device has been found, the device type will be displayed
on the screen. The LED on the device will stay lit until the device
has been successfully added to the system. The device number and
zone for the new unit should be selected using the cursor keys. You
will now be prompted to choose from using either the device
default settings set by the control panel or to manually set the
options. All options are entered using the cursor keys. Once you
have chosen the options, press
Enter
to program.
When adding a heat detector to the system, the user can select one of four operating modes:
Fixed Point
The device will go into alarm once the temperature reaches this point. The user
can specify an alarm temperature from 50 – 99
o
C.
Rate of Rise The device will go into alarm when it senses a rapid increase in temperature. The
user can choose from 3 levels of sensitivity.
A1S
As specified by EN54 part 5, A1S detectors are intended for use in applications
where the ambient temperature is typically around 25
o
C and not expected to
exceed 50
o
C. A1S detectors will not respond below their minimum static
response temperature of 54
o
C. A1S is the default setting.
A1R
As specified by EN54 part 5, an A1R detector is a rate of rise detector with a fixed
upper limit of 57
o
C, at which the device will go into alarm if the rate of rise has
been too slow to trigger the alarm earlier.
Device Programming
ENTER to continue
Device Scan
/
Please Wait
Device Found
HEAT/SOUNDER
A1S
Use ← → keys