EDA-Z5008, Z5020 & Z5100 – Technical Manual
ZPControlTechMan_r105
_____________________________________________________________________________________________________
5
Specification
Maximum Number of Zones
EDA-Z5008
8
EDA-Z5020
20
EDA-Z5100
100
Maximum Number of Devices
240
Maximum Number of Repeater Panels
7
Maximum Total Number of Antennas
15
Dimensions (W x H x D)
(not including antenna)
275x220x85mm
Weight (not including battery)
4kg
Operational Temperature
-5
o
C to +40
o
C
IP Rating
IP30
Alarm Indicators
Twin flashing red LEDs
Red individual zone LEDs
Fire message on LCD with 40 characters of text
Fault Indicators
Amber LEDs and LCD providing details and location of fault
with 40 characters of location text
Event Log Memory
1000 events maximum
Mains Supply
230V 50Hz 0.3A max
Mains Fuse
1 x 250V 3.15A
Battery
1 x 12V 7.0Ah sealed lead acid giving 72 hour standby
Battery Fuse
1 x 250V 3.15A
Relay Fuses
4 x 250V 500mA
RS485 Fuse
1 x 250V 500mA
Inputs
2 x wired monitored circuit. 4k7Ω (±5%) end of line (EOL)
resistor monitored for open and short circuit, 470Ω (±5%)
alarm load
Relays
4 x programmable
Relay Types
Fire Relay
Clean Contact
Fault Relay
Clean Contact
Sounder Circuit
10-18V, 500mA, 4k7Ω (±5%) EOL
Fault Relay Safe
Clean Contact
Fire Routing Relay
10-18V, 500mA, 4k7Ω (±5%) EOL
Operating Frequency
868MHz (868.025 to 868.575MHz)
Modulation
2-GFSK
Output Power (ERP)
<25mW (<14dBm)
Channel Spacing
50KHz
Error Checking
CRC
Error Correction
Hamming
Number Of Channels Available
12
Compatible With
Zerio Plus products only
Protocol
ZPNet V1.00