EDA-Z5008, Z5020 & Z5100 – Technical Manual
ZPControlTechMan_r105
_____________________________________________________________________________________________________
7
1.0 - EN54 Approved Configuration
The Zerio Plus system has been approved by Intertek to meet EN54 parts 2 and 4. The panels were
tested and approved in their default configuration. This manual lists all available panel options and
settings, some of which can be set in a way that would result in a system that does not comply with
EN54. The EN54 approved settings are listed below:
Setup Type:
Standard
Test Mode Type:
By Zone
Test Mode Timeout:
0
Relay 1:
Fire Routing Relay
Relay 2:
Fault Relay safe
Relay 3:
Sounder circuit
Relay 4:
Sounder circuit
Relays:
FIRE & SOUNDERS ON
Panel Buzzer:
Enabled
Code Protect:
ON
Device Verify Time:
390 seconds or less
Sounder Tone:
Swept
Input Type:
Latching
Input Relay Options:
Relays Off
Fire & Sounders On
Heat Detector Type:
A1S
Fault Relay:
Enabled
Device Faults:
Enabled
Panel Faults:
Enabled