EDA-Z5008, Z5020 & Z5100 – Technical Manual
ZPControlTechMan_r105
_____________________________________________________________________________________________________
22
6.8 - User Options – commissioning users
1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>1.Panel Options>>1.User Options
Detailed below are the other options that can be changed related to the panel. The default settings
have been type approved. Selecting some of the available options may result in a system which is not
EN54-2 approved. If unsure, contact EDA for advice.
Panel Zone
The zone the panel is located in.
Func Key
Set the function key as disabled, evacuate, alert or delay toggle.
Func Tone
The tone to be sounded if the function key is pressed and has been programmed
as either evacuate or alert.
The SWEPT tone has been type approved.
Func Relay
The relay to be operated if the function key is pressed and has been
programmed as either evacuate or alert.
The FIRE & SOUNDERS ON setting has
been type approved.
Double Knock
Whether double knock is enabled. See 14
.
0 – Delays.
Double Knock Tone
The tone to be sounded after second device activates.
The SWEPT tone has been
type approved.
Double Knock Relay
The relay to be operated after second device activates.
The FIRE & SOUNDERS
ON setting has been type approved.
Double Knock Zone
Whether a second device in the same zone or any second device
operates the double knock.
Relay 1 Type
Choose relay type 0 to 5. Default setting is 5.
FIRE ROUTING has been
type approved.
Relay 1 Reset
Whether Relay 1 is cleared upon pressing silence or upon pressing reset.
Relay 2 Type
Choose relay type 0 to 5. Default setting is 4.
FAULT RELAY SAFE has been
type approved.
Relay 2 Reset
Whether Relay 2 is cleared upon pressing silence or upon pressing reset.
Relay 3 Type
Choose relay type 0 to 5. Default setting is 3.
SOUNDER has been
type approved.
Relay 3 Reset
Whether Relay 3 is cleared upon pressing silence or upon pressing reset.
Relay 4 Type
Choose relay type 0 to 5. Default setting is 3.
SOUNDER has been
type approved.
Relay 4 Reset
Whether Relay 4 is cleared upon pressing silence or upon pressing reset.
The relay types are listed below:
Type 0
Disabled
Type 1
Fire Relay
Type 2
Fault Relay
Type 3
Sounder circuit
Type 4
Fault Relay Safe
Type 5
Fire Routing Relay
The relay types are configured not only in the panel software but also by physically placing jumper
links on the panel PCB. Refer to page 11 for relay link positions and fuse requirements.
To ensure EN54-2 compliance refer to section 1.0 of this manual for default settings. The panel was
type approved in this configuration.
Relay1 Type 5↕
Fire Routing Relay
Use ← → keys