background image

EDA-Z5008, Z5020 & Z5100 – Technical Manual  

 

ZPControlTechMan_r105 

_____________________________________________________________________________________________________ 

 

25 

 

6.15 - Input Options – commissioning users 

1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>2.Panel Inputs>>1.Input Options 

This menu allows the user to set options for the two monitored inputs. The default settings have been 
type  approved.  Selecting  some  of  the  available  options  may  result  in  a  system  which  is  not  EN54-2 
approved. If unsure, contact EDA for advice. 

 

Select Input 

Choose from input 1 or 2. 

 

IP Type  

Disabled, Latching IP, Non-latching IP or keyswitch. 

Latching IP is type approved. 

 

Zone 

 

Zone number of the hardware connected to the input.  

 

Delay1   

First delay before the sounders operate. 

 

Tone1   

Tone that the sounders sound after delay1. 

The SWEPT tone has been type approved.

 

 

Area1   

The area that should sound after delay1 (sounders will have to be programmed to this  

 

 

 

area to operate); see 6.34 – Reprogram Device. 

 

Relay1   

Hardwired relay operation in the panel after delay1. 

Types 0 and 3 are type approved. 

 

Delay2   

Second delay before the sounders operate. 

 

Tone2   

Tone that the sounders sound after delay2.

 The SWEPT tone has been type approved.

 

 

Area2   

The area that should sound after delay2. 

 

Relay2   

Hardwired relay operation in the panel after delay2.

 Types 0 and 3 are type approved.

 

 

These are the available relay types for the 

‘Input Options’

 menu. 

0. 

 

Relays Off

 

 

1. 

 

Sounders Pulse 1 

2. 

 

Sounders Pulse 2 

3. 

 

Fire & Sounders On

 

 

4. 

 

Fire On 

5. 

 

Sounders On 

6. 

 

Fire & Sounders Pulse 1 

7. 

 

Fire & Sounders Pulse 2 

8. 

 

User Relay A 

9. 

 

User Relay B 

10. 

 

User Relay C 

11. 

 

User Relay D 

 

6.16 - Input Text – commissioning users 

1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>2.Panel Inputs>>2.Input Text 

This  menu  allows  the  user  to  assign  text  names  to  each  of  the 
inputs.  Select  the  input,  then  enter  text  using  the  panel  or  by 
connecting a standard USB keyboard. Press 

Enter

 to save. Multiple 

devices connected to an input (i.e. hardwired detectors) cannot be 
individually assigned text names. 
 

6.17 - Keyswitch Options – commissioning users 

1.Main Menu>>1.Setup>>4.System Setup>>3.Edit Panel>>2.Panel Inputs>>3.Keyswitch Options

 

This menu allows the user to set up a keyswitch on the inputs. 
 

 
 
 
 
 

    Text Location 
   

  ↑ show characters  

Summary of Contents for EDA-Z5008

Page 1: ...ZERIO PLUS EDA Z5008 Z5020 Z5100 INSTALLATION OPERATION MANUAL ZPControlTechMan_r105 Revision 1 05...

Page 2: ...s EN54 2 1997 A1 2006 EN54 4 1997 A1 2002 A2 2006 EN54 25 2008 Control and indicating equipment for fire detection and fire alarm systems for buildings Models EDA Z5008 EDA Z5020 EDA Z5100 Optional fu...

Page 3: ...is achieved by radio Text locations can be entered on the panel itself or by connecting a standard USB keyboard to the panel Devices for the system are visually the same as the standard Millennium an...

Page 4: ...evel descriptions V0 13 07 10 2013 Updated PCB layout V0 14 14 10 2013 Filename change DOP updated V0 15 17 10 2013 EN54 approved functions added Formatting changes V1 00 21 10 2013 First release V1 0...

Page 5: ...ion of fault with 40 characters of location text Event Log Memory 1000 events maximum Mains Supply 230V 50Hz 0 3A max Mains Fuse 1 x 250V 3 15A Battery 1 x 12V 7 0Ah sealed lead acid giving 72 hour st...

Page 6: ...Keyswitch Options 6 18 Panel Text 6 19 SIM Operations 6 20 Device Assignment 6 21 Panel Assignment 6 22 Add Antenna 6 23 Add Repeater Booster Panel 6 24 Add Pager 6 25 Remove Hardware 6 26 Panel Netwo...

Page 7: ...and settings some of which can be set in a way that would result in a system that does not comply with EN54 The EN54 approved settings are listed below Setup Type Standard Test Mode Type By Zone Test...

Page 8: ...ely isolated before working on any mains rated components Cables should only enter the panel housing through the knockouts provided Do not remove more knockouts than is needed to terminate the cables...

Page 9: ...laced The battery voltage can be viewed on the PSU Info section of the 6 5 Panel Info menu When replacing the battery always do so with a product of equal specification Always dispose of batteries res...

Page 10: ...A suitable data cable should be used with 2 sets of twisted pairs Cat 5 5e 6 can be used but is not fire rated Wired antennas and displays have two RS485 connectors making it possible to make a chain...

Page 11: ...free clean contact relays The relay type can be changed in 6 8 User Options and by positioning the jumper links and fuses as detailed below When relays are configured as fire routing or as sounder cir...

Page 12: ...fire condition exists across multiple zones multiple zone LEDs will be illuminated The EDA Z5008 8 Zone panel is shown The EDA Z5020 panel is equipped with 20 zone LEDs and the EDA Z5100 is equipped...

Page 13: ...ed by default though it can be programmed to do a number of functions See 6 8 User Options Cancel Used to return to the main screen from a menu or to return to the menu from a programming screen Enter...

Page 14: ...he fault has been acknowledged and does not re sound the buzzer unless a new fault occurs The LED on the device will continue to flash until the fault is reset see below 4 4 Reset a Fault A fault will...

Page 15: ...system can be silenced and reset without a code by turning off Code Protect see 6 9 System Options If a device has remained in alarm i e the glass has not been replaced in a callpoint or a smoke detec...

Page 16: ...ain Menu 4 View Events 2 View Event Log If a non menu screen is selected the Cancel button should be pressed to return to the menu without making any changes Subsequently then pressing Cancel for a se...

Page 17: ...Menu 1 Setup 2 Access Codes 2 Change Codes Using the cursor keys select the access level for which the access code is to be changed Users can only change the access code for their level and below Once...

Page 18: ...de the characters and press Confirm the text is correct and press Enter to save To return to the menu press Cancel Change Display Options service and commissioning users 1 Main Menu 1 Setup 3 Panel Di...

Page 19: ...indicator from 20 to 20 RF Chan The channel the system is using Pan The number of the panel programmed at the antenna Slot Device protocol slot Squelch RF interference filter Non user adjustable View...

Page 20: ...emoval button down while you place the jumper link to the ON position 2 If a sounder beacon callpoint transmitter or I O unit is being programmed hold down the unit removal button while holding a magn...

Page 21: ...either a common zone or a dwelling zone The zone designation will affect how the system reacts to an alarm within the zone The zone designation can be changed later in the HMO Zones menu Once complet...

Page 22: ...ctivates The FIRE SOUNDERS ON setting has been type approved Double Knock Zone Whether a second device in the same zone or any second device operates the double knock Relay 1 Type Choose relay type 0...

Page 23: ...h goes into alarm will cause the sounders to start sounding again 6 10 Fault Options commissioning users 1 Main Menu 1 Setup 4 System Setup 3 Edit Panel 1 Panel Options 3 Fault Options This menu allow...

Page 24: ...iggered Evac Relay This relay can be set to on off or pulse when the Evac tone is being sounded React Time If an alert is not silenced within this time period the system will trigger an evacuation Ven...

Page 25: ...e panel after delay1 Types 0 and 3 are type approved Delay2 Second delay before the sounders operate Tone2 Tone that the sounders sound after delay2 The SWEPT tone has been type approved Area2 The are...

Page 26: ...device to the panel or antenna it receives the strongest signal from This can be done for one device or for all devices at once Be sure to clear the verify table first and wait 15 minutes before runn...

Page 27: ...t the next available panel number the main panel is always panel 01 When prompted the memory card from the repeater panel will need to be placed into the memory card slot of the main panel Do not mix...

Page 28: ...ar Network The clear network option will remove any current network set up from a system It will clear the local panel currently being used the repeater panels on the network and clear the verify tabl...

Page 29: ...1 Main Menu 1 Setup 5 Device Setup 1 Device Info 3 Device Version Select a device and press Enter to poll that device This will display the version number of the firmware on the selected device Devic...

Page 30: ...pe will be displayed on the screen The LED on the device will stay lit until the device has been successfully added to the system The device number and zone for the new unit should be selected using t...

Page 31: ...ons have been edited press until press Enter to save is displayed Zone The zone the device is located in Delay1 The first delay before the sounders operate Tone1 The tone that the sounders should oper...

Page 32: ...Once the device has been found the device type will be displayed on the screen The LED on the device will stay lit until the device has been successfully reprogrammed The device number for the new un...

Page 33: ...r can disable a zone indefinitely by selecting a time of 00 hours Press Enter to save the change Device XXX disabled will be displayed on screen and the LED marked Disablements will now be illuminated...

Page 34: ...led will automatically be enabled again When Fire Routing is disabled open circuit and short circuit faults will not be reported Disable Fault Relay all access levels 1 Main Menu 2 Disable Enable 1 Di...

Page 35: ...ces zones remain then the Disablements LED will extinguish Enable Panel Input all access levels 1 Main Menu 2 Disable Enable 2 Enable 3 Panel Input Select this option to enable an input that has previ...

Page 36: ...NO SOUND Alternatively the sounders can be set to 6 SEC SOUND where any activated sounders will automatically silence after 6 seconds This allows the engineer to perform a one man walk test without t...

Page 37: ...s to be disabled in an alarm test Beacons Choose from Off or On Callpoint Override When set to Yes callpoints will cause an alarm and sounders will sound if operated in test mode If set to No callpoin...

Page 38: ...in Menu 4 View Events 3 Clear Event Log The event log can be cleared by selecting 3 Clear Event Log and then pressing Enter to confirm 9 4 Dump the Event Log to a USB Flash Drive commissioning users 1...

Page 39: ...g 10 1 View a Summary of Verify Information for a Single Device service and commissioning users 1 Main Menu 5 Verify Table 1 View Table 1 View Summary From the Verify Table menu select 1 View Table Se...

Page 40: ...ved transmission Screen 2 By using the cursor key the screen opposite will appear This screen details the number of times the device has failed to transmit within the time period shown This informatio...

Page 41: ...e 4 Panel Table The panel table gives the user the same information as the verify table but for any panels on the system rather than devices As with the verify table users can view a summary of the in...

Page 42: ...ew All Displays every signal received on current RF channel View This System Only messages from devices that have been previously programmed on to this system will be listed View Single Device Only me...

Page 43: ...TYPE ERROR The device reporting to the panel does not match the device information stored on the panel TX RX FAULT Transceiver fault VERIFY FAULT Panel has lost communication with a device 13 2 Panel...

Page 44: ...Key as a Delay Toggle Switch 1 Main Menu 1 Setup 4 System Setup 3 Edit Panel 1 Panel Options 1 User Options Press the key until the function key screen is displayed Use the and keys to select delay to...

Page 45: ...compatible with the Q690 batteries How do I disable the sounders See 8 0 Test Mode or select disable sounders in the 7 0 Disable Enable menu What is a removal fault This fault is to alert the user to...

Page 46: ...5 of detectors and 100 of callpoints The devices tested should be varied so that each device will have been tested at some point in any given 12 month period The panel battery connections and any rela...

Page 47: ...anel has powered up before reconnecting the battery Display Board Power down the panel by disconnecting the battery and removing the mains fuse from the terminal block Unplug the ribbon cable from the...

Page 48: ...x EDA Q690 EDA T5000 Radio Transmitter Unit 1 x EDA Q690 EDA T5100 Radio Silence Alarm Button 1 x EDA Q690 EDA T6080 Radio Input Output Unit DC 1 x EDA Q690 EDA Y5000 Dipole Weatherproof Antenna EDA Z...

Reviews: