EDA-Z5008, Z5020 & Z5100 – Technical Manual
ZPControlTechMan_r105
_____________________________________________________________________________________________________
34
Disable Sounders – all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>4.Sounders
The sounders can be disabled for a period of time specified by the user, dependent on their access
level. All access levels can disable a sounder for a period of 1 to 96 hours. A commissioning user can
disable a sounder indefinitely by selecting a time of ‘00’ hours. The sounders will ignore any fire event
from the panel within that time. Both the ‘Disablements’ LED and the ‘Sounder Flt/Disable’ LED will be
illuminated. After the timeout period has elapsed any disabled sounders will automatically be enabled
again. When sounders are disabled, any hard wired sounder circuits will not display short circuit and
open circuit faults.
Disable Fire Routing – all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>5.Fire Routing
The fire routing relay can be disabled for a period of time specified by the user, dependent on their
access level. All access levels can disable the relay for a period of 1 to 96 hours. A commissioning user
can disable the relay indefinitely by selecting a time of ‘00’ hours. The relay will ignore any fire event
from the system within that time. The ‘Disablements’ LED and the ‘Routing Flt/Disable’ LED will be
illuminated. After the timeout period has elapsed, the relay (if still disabled) will automatically be
enabled again. When Fire Routing is disabled, open circuit and short circuit faults will not be reported.
Disable Fault Relay – all access levels
1.Main Menu>>2.Disable/Enable>>1.Disable>>6.Fault Relay
The fault relay can be disabled for a period of time specified by the user, dependent on their access
level. All access levels can disable the relay for a period of 1 to 96 hours. A commissioning user can
disable the relay indefinitely by selecting a time of ‘00’ hours. The relay will ignore any fault event from
the system within that time. After the timeout period has elapsed, the relay (if still disabled) will
automatically be enabled again. To comply with EN54, the fault relay should not be disabled.
Disable Device Fault – commissioning users
1.Main Menu>>2.Disable/Enable>>1.Disable>>7.Device Fault
It is possible to disable a type of fault from a specific device for a period of 1 to 16 weeks. Faults can be
disabled indefinitely by selecting a timeout of ‘00’ hours. First select the device number, select the fault
type you wish to disable and the timeout period. After the timeout period has elapsed, any disabled
faults will automatically be enabled again. To comply with EN54, a device fault should not be disabled.
Disable Panel Fault – commissioning users
1.Main Menu>>2.Disable/Enable>>1.Disable>>8.Panel Fault
It is possible to disable a specific type of fault from the control panel for a period of 1 to 16 weeks.
Faults can be disabled indefinitely by selecting a timeout of ‘00’ hours. After the timeout period has
elapsed, any disabled faults will automatically be enabled again. To comply with EN54, a panel fault
should not be disabled.