YOKOGAWA DPharp EJXC40A User Manual Download Page 93

  

<7.  HART Communication>

7-40

IM 01C25W05-01EN

●  Invalid Ref BlkF, Pres 1, Pres2, or DP

This alarm indicates that the reference value 

acquired under normal process conditions 

is invalid. If the Ref BlkF value is invalid as a 

reference value, only the blockage detection 

that excludes the BlkF detection algorithm is 

executed. If you need blockage detection that 

uses the BlkF algorithm, reacquire Ref BlkF.

If Ref DPAvg falls below the Lim DPAvgmin 

threshold or exceeds the Lim DPAvgmax 

threshold, all reference values will be invalid. 

If this occurs, alarms for all reference values 

(Invalid Ref DP, Invalid Ref Pres 2, Invalid Ref 

Pres 1, and Invalid Ref BlkF) will be generated.

■ Alarm masking

●   Diag Option

Select which alarms will be reflected in analog 

alerts and LCD display using the Diag Option 

parameter.

•  Recalling the Diag Option parameter

Recall 

parameters

[Root menu] → Diag/Service → Diag 

Parameters → Diag Option

Each bit of the Diag Option parameter 

corresponds one-to-one to the bits of the Diag 

Error parameter.
By factory default, the following alarms are 

enabled (hexadecimal notation: 0x08f8).

Bit

Assignment

3

Large Fluct Pres 2

4

Large Fluct Pres 1

5

Pres 2 Side Blocking

6

Pres 1 Side Blocking

7

B Blocking

11

Invalid Ref DP

To reflect alarms in analog alerts and LCD 

display, follow the procedure below.
1) Set the Diag Mode parameter to Stop.

2) From the alarms assigned to bits 2 to 14, 

select the check boxes of the required 

alarms.

■ Analog alert setup

●  Diag Out Option

If impulse line blockage error or high-

temperature/low-temperature flange 

temperature error occurs, the 4-20 mA analog 

output can be shifted according to the specified 

settings.

•  Recalling the Diag Out Option parameter

Recall 

parameters

[Root menu] → Diag/Service → Diag 

Parameters → Diag Output → Diag Out 

Option 

Mode

Function

Off

The PV measurement is held, and alarm 

occurrences are not reflected in the output.

Burnout When an alarm occurs, the analog output is 

shifted to the value specified in the AO upper 

limit parameter or AO lower limit parameter. 

The direction in which the output is shifted 

depend s on the Burnout switch setting.

Fall back When an alarm occurs, the output is held 

at a certain value. The shift value can be 

specified using the Diag Fixed Out Val 

parameter.

● Diag Fixed Out Val

This is used when the Diag Output Option 

parameter is set to Fall back.

When an alarm occurs, the output is held at the 

value specified with this parameter. You can 

enter the value in the range of 3.8 to 21.6 mA.

•  Recalling the Diag Fixed Out Val parameter

Recall 

parameters

[Root menu] → Diag/Service → Diag 

Parameters → Diag Output → Diag 

Fixed Out Val →

Summary of Contents for DPharp EJXC40A

Page 1: ...User s Manual Digital Remote Sensor IM 01C25W05 01EN IM 01C25W05 01EN 4th Edition...

Page 2: ...adio Transceivers 2 3 2 8 Insulation Resistance and Dielectric Strength Test 2 3 2 9 Installation of an Explosion Protected Instrument 2 4 2 9 1 FM Approval 2 4 2 9 2 ATEX Certification 2 9 2 9 3 IECE...

Page 3: ...1 Preparation for Starting Operation 6 1 6 2 Zero Point Adjustment 6 2 6 3 Starting Operation 6 3 6 4 Shutting Down Operation 6 3 6 5 Venting or Draining Transmitter Process Detector Section 6 3 6 5...

Page 4: ...ail Setup 7 8 7 2 3 1 Pressure Signal Setup 7 8 7 2 3 2 Pressure Damping Time Constant 7 8 7 2 3 3 Impulse Line Connection Orientation Setup 7 9 7 2 3 4 Bi directional Flow Measurement Setup 7 9 7 2 3...

Page 5: ...hecking the Blockage Detection Operating Capacity 7 42 7 3 2 2 9 ILBD Execution 7 43 7 3 2 2 10 Tuning 7 43 7 3 2 2 11 Resetting the Reference Value 7 45 7 3 2 2 12 ILBD Parameter List 7 45 7 3 2 3 He...

Page 6: ...3 Setup A1 1 A1 2 4 Required Parameter Settings A1 1 A1 2 5 Proof Testing A1 1 A1 2 6 Repair and Replacement A1 2 A1 2 7 Startup Time A1 2 A1 2 8 Firmware Update A1 2 A1 2 9 Reliability Data A1 2 A1 2...

Page 7: ...l and the transmitter body section style code written on the product nameplate F0101 ai DRS cable High pressure side transmitter master Low pressure side transmitter slave Screw mounting Digital remot...

Page 8: ...NOTE When describing the model name like EJ 530 it shows the applicability for EJX530A Regarding This Manual This manual and the identification tag attached on the packing box are essential parts of...

Page 9: ...t heeded the protection provided by this instrument may be impaired In this case Yokogawa cannot guarantee that the instrument can be safely operated Please pay special attention to the following poin...

Page 10: ...e time of purchase Problems occurring during the warranty period shall basically be repaired free of charge If any problems are experienced with this instrument the customer should contact the Yokogaw...

Page 11: ...U bolt L U bolt S U bolt S nut Figure 2 1 Transmitter Mounting Hardware 2 1 Model and Specifications Check The model name and specifications are written on the name plate attached to the case Look up...

Page 12: ...thermal insulation and or ventilation Also avoid locations subject to prolonged high temperature and high humidity Ambient Atmosphere Do not install the transmitter in a corrosive atmosphere If this c...

Page 13: ...erminals in the terminal box 4 Turn OFF the insulation tester Then connect the insulation tester plus lead wire to the shorted SUPPLY terminals and the minus leadwire to the grounding terminal 5 Turn...

Page 14: ...setting switch must not be used in a hazardous area IMPORTANT For combined approval types Once a device of multiple approval type is installed it should not be re installed using any other approval t...

Page 15: ...n installing the equipment In case Nonincendive Field Wiring Concept is used for the interconnection FM approved Associated Nonincendive Field Wiring Apparatus which meets the following conditions mus...

Page 16: ...2 Handling Cautions 2 6 IM 01C25W05 01EN Note 6 Control Drawing...

Page 17: ...2 Handling Cautions 2 7 IM 01C25W05 01EN...

Page 18: ...2 Handling Cautions 2 8 IM 01C25W05 01EN...

Page 19: ...vices in a hazardous location Note 4 Maintenance and Repair The instrument modification or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and...

Page 20: ...ment Note 5 Specific Conditions of Use WARNING Precautions shall be taken to minimize the risk from electrostatic discharge of painted parts When the enclosure of the Pressure Transmitters is made of...

Page 21: ...nd Repair WARNING The instrument modification or parts replacement by other than an authorized Representative of Yokogawa Electric Corporation is prohibited and will void the ATEX certification Note 6...

Page 22: ...5 female ANSI 1 2 NPT female M N or W 3 Installation WARNING All wiring shall comply with local installation requirements and the local electrical code 4 Operation WARNING OPEN CIRCUIT BEFORE REMOVING...

Page 23: ...in the event of rare incidents an ignition source due to impact and or friction sparks is excluded Model EJX P and EJA P series pressure transmitters are not capable of withstanding the dielectric str...

Page 24: ...Certification Electrical Connection A mark indicating the electrical connection type is stamped near the electrical connection port These marks are as followed F0206 ai Location of the mark Screw Siz...

Page 25: ...X PROCESS TEMP 120 C Supply Output Ui 30V Ii 200mA Pi 0 9W Ci 27 6nF Li 0mH Communication Uo 8 2V Io 160mA Po 0 3W Co 7 6 F Lo 1mH POTENTIAL ELECTROSTATIC CHARGING HAZARD SEE USER S MANUAL KS24 S No F...

Page 26: ...Note 2 Set the switches BO WR as shown in the figure above to set the burn out direction for CPU errors and write protection The Burnout switch is set to the H side for delivery unless option code C1...

Page 27: ...cription 3 2 IM 01C25W05 01EN 3 2 Low Pressure Side Transmitter Slave F0302 ai Transmitter CPU assembly DRS cable connection port Amplifier cover Figure 3 2 Component Names of the Low Pressure Side Tr...

Page 28: ...lead to leaks Zero adjustment screw Pipe back side of the instrument F0401 ai Figure 4 1 Pipe and Zero Adjustment Screw 4 2 Mounting IMPORTANT As the pressure detector diaphragm is thin and prone to d...

Page 29: ...eting IMPORTANT Tighten the hexagonal nut part of the capsule assembly See Figure 4 4 Pressure detector section F0404 ai Figure 4 4 Tightening Transmitter F0405 ai Gasket Stud bolt Nut Figure 4 5 Moun...

Page 30: ...e Figure 4 9 Correctly install the diaphragm seal part on the tank checking the label PRESSURE HIGH or PRESSURE LOW on each seal Exercise care so as not to damage diaphragm surfaces For models with di...

Page 31: ...you connect the power supply directly it may damage the equipment 4 4 Mounting the C10FR Flushing Connection Ring 4 4 1 Mounting to Pressure Detector Section The C10FR flushing connection ring is moun...

Page 32: ...re mounting the ring use the new spiral gasket as shown in below table Table 4 1 Spiral Gasket for Pressure Detector Section Side Hoop material Part number Gasket size Description SUS316 SUS316L Hast...

Page 33: ...rt No F9145YN Gasket contact surface F0412 ai Diaphragm seal section Figure 4 14 Affixing the Teflon Film 4 6 Tank Spud Mounting Method A tank spud is used to joint a tank and an extended diaphragm It...

Page 34: ...uck to the surface Special Tools for Tank Spud Welding Yokogawa provides special tools exclusively designed for the tank spud welding to make the installation easily and effectively These tools can be...

Page 35: ...tscrews securing the transmitter section to the capsule assembly 2 Rotate the transmitter section slowly to the desired position 3 Tighten the two setscrews to a torque of 1 5 N m 15 kgf cm IMPORTANT...

Page 36: ...e shielded wires in areas that are susceptible to electrical noise In areas with higher or lower ambient temperatures use appropriate wires or cables In environment where oils solvents corrosive gases...

Page 37: ...a two wire transmission system signal wiring is also used as power wiring DC power is required for the transmitter loop The transmitter and distributor are connected as shown below For details of the...

Page 38: ...an be run through a cable gland or a wiring metal conduit In either method follow the procedure below to connect and disconnect wiring CAUTION In the case of the flameproof type running the wires thro...

Page 39: ...2NPT Type M20 Type Gasket Entry with Seal Running Coupler Backnut Entry with Seal Running Coupler Backnut F0511 ai Figure 5 11 Components of the Cable Gland Installing the cable gland 1 Disassemble t...

Page 40: ...ods side opposite side of DRS connector before laying the cable Procedure 1 Disassemble the cable gland loosen the all parts 2 Remove the protection cap on the DRS electrical connection and DRS connec...

Page 41: ...ugh the wiring metal conduit and screw the conduit into the wiring port CAUTION Do not pull on the cable or apply excessive mechanical shock to it 5 5 3 Removing DRS Cable with Cable Gland 1 Slowly re...

Page 42: ...tion of transmitters Follow the domestic electrical requirements as regulated in each country Ground terminals are located on the inside and outside of the terminal box Either of these terminals may b...

Page 43: ...roperly Check parameter values or change the setpoints as necessary See chapter 7 for the operating procedure of the HART configuration tool If the transmitter is equipped with an integral indicator i...

Page 44: ...d and confirm the value b Adjust output to the reference value obtained using other means In tank level measurement if the actual level cannot be brought to zero for zero adjustment then the output ca...

Page 45: ...er cover Screw each cover in tightly until it will not turn further There are two covers that must be locked on the ATEX Flameproof type transmitters An Allen head bolt shrouding bolt under the edge o...

Page 46: ...as will be expelled in the direction of the arrow F0605 ai Figure 6 5 Draining Condensate from C10FR Flushing Connection Ring 6 5 2 Venting Gas from C10FR Flushing Connection Ring 1 Gradually open the...

Page 47: ...CD update will be slower at low ambient temperature and it is recommended to use LPS function at temperatures above 10 C 6 6 1 Local Parameter Setting LPS Overview Parameter configuration by the zero...

Page 48: ...the value Save Cancel the value 6 Output Mode 2 DP Unit 1 Tag Number 3 DP LRV 4 DP URV 7 Display Out1 8 LRV Apply Press 9 URV Apply Press 5 Damping Time Select Output mode Select DP unit Edit Tag numb...

Page 49: ...below parameters are shown sequentially by each press of the push button Tag number Unit LRV URV Damping Output mode linear square root signal characterizer Display out 1 F0611 ai push push push push...

Page 50: ...etween the various available pressure units F0612 ai screw push Select by the push button Blinking Blinking Save Cancel Available units kPa bar inH2O 4degC 39 2degF Torr mbar inH2O 20degC 68degF atm g...

Page 51: ...or the differential prressure transmission part can be set Damping time constant is rounded off to two decimal places F0613 ai screw Change the first digit Set all other characters in the same way Set...

Page 52: ...pletes the LRV setting Note 3 6 Press the push button The integral indicator then displays URV SET 7 Apply a pressure of 3 MPa to the transmitter Note 1 8 Turn the external adjustment screw in the des...

Page 53: ...ter 6 6 13 Local Parameter Setting Lock To disable parameter changes by the Local Parameter Setting there are three different ways Locked features Communication Parameter Ext SW disable External Zero...

Page 54: ...he slave transmitter for low pressure side measurement 7 1 Connection 7 1 1 Integral Indicator Display at Power On If the transmitter is equipped with the integral indicator when the EJXC40A digital r...

Page 55: ...ansmitter and DD by following steps 1 and 2 If the appropriate DD is not installed in the configuration tool download it from the official HARTAssociation website or contact the configuration tool dis...

Page 56: ...nsmission loop The configuration tool is connected in parallel with the transmitter but the polarity does not matter A connection example is shown below USB FieldMate Modem Relay terminals Distributor...

Page 57: ...x y z SP represents one byte space 7 2 2 2 Setting Process Variables The transmitter can handle five types of data these are called device variables differential pressure DP module 1 side pressure Pr...

Page 58: ...Measuring Range These range values are set as specified in the order before the instrument is shipped Follow the procedure below to change the measuring range You can enter the low limit LRV and high...

Page 59: ...ime constant follow the procedure below Recalling the damping time constant parameter DP damp Recall parameters Root menu Detailed setup Sensors DP setup DP damp Enter a valid time constant in the DP...

Page 60: ...the low cut value for the output signal is 1 and that for the integral indicator display is 10 which is equivalent to the square root of the low cut value Note that if the output mode is set to Sq ro...

Page 61: ...pressure units are shown below inH2O 68degF inHg ftH2O 68degF mmH2O 68degF mmHg psi bar mbar g cm2 kg cm2 Pa kPa torr atm MPa inH2O mmH2O ftH2O hPa 2 Setting the low limits Pres 1 LRV Pres 2 LRV and h...

Page 62: ...rameters Recall parameters Root menu Detailed setup Signal condition Pres 1 2 Swap Select Normal or Reverse 7 2 3 4 Bi directional Flow Measurement Setup This parameter enables output whose positive a...

Page 63: ...ke sure that the upper limit and lower limit satisfy the following relationship Lower limit Upper limit 7 2 3 6 Integral Indicator Display Mode The mode setting for the output signal see subsection 7...

Page 64: ...age PV Differential pressure DP Module 1 side pressure Pres 1 Module 1 side capsule temperature Temp 1 Module 2 side pressure Pres 2 Module 2 side capsule temperature Temp 2 User set scale PV value En...

Page 65: ...following when entering the unit directly Up to eight characters can be set using alphanumeric characters and a slash but only the first six characters are displayed If two or more slashes or any of t...

Page 66: ...suring range is zero Recalling and setting the zero point adjustment parameter DP Zero trim Recall parameters Root menu Maintenance DP trim DP Zero trim Confirm the value after it has stabilized ON th...

Page 67: ...g and setting automatic adjustment parameters Recall parameters Root menu Maintenance DP trim DP trim method Auto Lower Pt Set the low limit value you want to adjust Auto Upper Pt Set the high limit v...

Page 68: ...ance Pres 1 trim Clear Pres 1 trim method Pres 2 Root menu Maintenance Pres 2 trim Clear Pres 2 trim method 7 2 3 10 Analog Output Adjustment This function adjusts the analog output value Two adjustme...

Page 69: ...outputs a 110 or higher signal For models with optional code C1 and C2 The switch is set to low L If an error occurs the transmitter outputs a 2 5 or lower signal The 4 to 20 mADC burnout direction f...

Page 70: ...and Y coordinate values Enter the values to assign to the X and Y coordinates using the Point setting parameter 3 Apply the signal characterizer function After setting the coordinate values setting p...

Page 71: ...tailed setup Output condition Process Alerts DPAlert Select differential pressure and set the threshold Pres 1 Alert Select module 1 side pressure and set the threshold Pres 2 Alert Select module 2 si...

Page 72: ...d To perform test output from the DTM recall Loop Test from Hot key menu select manual test or auto test in the figure on the screen and set the value 2 Device variable simulation A value and status o...

Page 73: ...ared F0711 ai Figure 7 2 9 Display during Squawk Execution 7 2 3 17 Burst Mode If burst mode is enabled the transmitter can continuously send three of the data shown in Table 7 2 4 through HART commun...

Page 74: ...lect up to 8 from differential pressure pressure capsule temperature percent of range and Loop current 2 Cmd9 Device vars w status Continuous Window Process variable assigned to the head of Burst Vari...

Page 75: ...d Burst Command Burst mode Burst Msg Trigger Mode Continuous Window Rising Falling On change Send to transmitter Cmd9 Cmd33 a Burst Command b Burst Variables c Update period and Max Update Period by S...

Page 76: ...parameters Burst Condition Burst Message1 2 or 3 Burst Variables Burst Variable Code DP Select the differential pressure Pres 1 Select the module 1 side pressure Pres 2 Select the module 2 side pressu...

Page 77: ...n Changes to device settings and changes to the device status through self diagnosis can be detected as events and alarm signals can be sent continuously Up to four events that occur are saved as hist...

Page 78: ...tification Control to Enable event notification on token passing data link layer 3 2 Acknowledging events DTM only When the host device acknowledges an event event transmission stops To acknowledge ev...

Page 79: ...nected to a single communication line To enable multidrop communication the device address must be set to any number ranging from 1 to 63 When set to multidrop mode all data are sent digitally Therefo...

Page 80: ...earches for devices set to multidrop mode If the HART configuration tool is connected to devices their polling addresses and tags are displayed 2 Selecting the device of your choice enables communicat...

Page 81: ...ess status Status group 5 14 Module 1 side setting status Status group 15 16 Diagnostic status Status group 17 Simulation status Status group 18 Module 2 side hardware status Status group 19 20 21 Mod...

Page 82: ...ime Stamp Current Date The number of running days is displayed January 1 1970 is the operation start date Current Time The running time is displayed NOTE Timestamps are reset when the power is turned...

Page 83: ...groups are displayed simultaneously 7 3 2 Advanced Diagnostics 7 3 2 1 What Is the Multi Sensing Process Monitoring Function The multi sensing process monitoring function optional code DG6 is a funct...

Page 84: ...in the BlkF values or module 1 side fluctuation The blockage level obtained by statistically comparing the pressure fluctuation between the module 1 side and module 2 side For details see subsection 7...

Page 85: ...o fP1 A value obtained by comparing the root mean square RMS of the module 1 side pressure fluctuation It is used for blockage detection Ratio fP1 SQRT fP1 Ref fP1 BlkF A value indicating the blockage...

Page 86: ...ou are using this for the first time use the default values If not enough pressure fluctuation can be detected in valve simulation tests or in actual operation or if alarms occur frequently refer to s...

Page 87: ...t Pres 2 low pressure side pressure fluctuation error is detected Determination of Pres 1 Side Blocking The BlkF value is prioritized in the determination of high pressure side blockage However if the...

Page 88: ...on fP2 and Ref fP2 Pres 1 Side Blocking detection based on fP1 and Ref fP1 Pres 1 Pres 2 Side Blocking detection based on BlkF Ref fDP OK Ref fP2 OK Ref fP1 OK Ref BlkF NG Low pressure side blockage...

Page 89: ...complete Diag Mode returns to the original mode NOTE If the impulse line blockage detection ILBD parameter is set using the Download to device of the DTM Diag Mode is automatically set to Stop Diag Pe...

Page 90: ...t threshold e g Lim fDPmin Alarm occurrence Alarm occurrence Time Time Figure 7 3 4 Relationship between Diag Supp Count and alarms The detection count applies to all error alarms The factory default...

Page 91: ...ILBD 1 2 Alarm masking Set the alarm to indicate through communication or on the LCD using the Diag Option parameter 3 1 Acquire reference values Acquire fluctuation data under steady state operation...

Page 92: ...Pres 1 10 Invalid Ref Pres 2 11 Invalid Ref DP 12 ILBD over Range 13 Flg Temp Low Alarm Heat trace monitoring 14 Flg Temp High Alarm 15 Not used ILBD over range 1 Lim DPAvgmax The Lim DPAvgmax paramet...

Page 93: ...ing 11 Invalid Ref DP To reflect alarms in analog alerts and LCD display follow the procedure below 1 Set the Diag Mode parameter to Stop 2 From the alarms assigned to bits 2 to 14 select the check bo...

Page 94: ...s pressure fluctuation is small blockage detection does not work properly The pressure fluctuation may be small in the case of level measurement or pressure measurement of tanks or when gases are meas...

Page 95: ...ference values automatically ends and the Diag Mode parameter switches automatically from Reference to Calculation Check that the sampling has finished by confirming that the Diag Mode has changed to...

Page 96: ...ters elapses check that Pres 1 Side Blocking and Pres 2 Side Blocking are indicated in the Diag Error parameter 5 If the analog output is configured to shift in response to the alarm occurrence check...

Page 97: ...ge the sampling period follow the procedure below 1 Set the Diag Mode parameter to Stop 2 Set the Diag Period parameter value in the range of 20 to 65535 seconds In addition increasing the detection c...

Page 98: ...ion results Reference The reference values are set to the latest blockage detection data When the reference values are updated the mode automatically switches to Calculation 6 Diag Period 180 sec This...

Page 99: ...ter can be entered only when Diag Mode is set to Stop 41 Lim BlkFmax Upper limit of one side blockage level BlkF used for impulse line blockage detection This parameter can be entered only when Diag M...

Page 100: ...ected in Diag DP Comp NRatio fDP is used as the monitoring value NRatio fDP Sqrt fDP Ref fDP 53 NRatio fDP Status Status of NRatio fDP 54 Diag DPComp Compensation Flow rate compensation flag Sets whet...

Page 101: ...High temperature error detection threshold Flg temp lo alert val Low temperature error detection threshold Formula Flg temp FT CT Cf CT AT CAUTION The flange temperature is calculated with the formula...

Page 102: ...e case of DTM the tuning function can be used to set Flg temp coef Enter the measured flange temperature to calculate Flg temp coef using the capsule temperature and amplifier temperature measured wit...

Page 103: ...put modes are Off Burnout and Fall back 4 Diag Fixed Out Val 21 6 mA A parameter for the fall back function in Diag Out option This specifies the output value of the 4 to 20mA analog signal when alarm...

Page 104: ...rocedures required for component replacement Transmitters are precision instruments Please carefully and thoroughly read the following sections for information on how to properly handle them while per...

Page 105: ...5 digits for 0 to 25 kPa 0 2 of rdg 0 1 of F S for 80 to 0 kPa 3 For 700 kPa class Accuracy 0 02 of rdg 3digits for 100 to 700 kPa 5 digits for 0 to 100 kPa 0 2 of rdg 0 1 of F S for 80 to 0 kPa 4 For...

Page 106: ...e should be applied to the high pressure side as shown in the Figure The low pressure side is released to the atmosphere If the measurement range 0 point is 0 kPa or shifted in the positive direction...

Page 107: ...lease pressures before disassembly Use proper tools for all operations Table 8 2 shows the tools required Table 8 2 Tools for Disassembly and Reassembly Tool Quantity Remarks Phillips screwdriver 1 JI...

Page 108: ...re 8 3 4 Disconnect the DRS output cable cable with white connector at the end 5 Use a socket driver width across flats 5 5mm to loosen the two bosses 6 Carefully pull the CPU assembly straight forwar...

Page 109: ...he Capsule Assembly IMPORTANT When cleaning the capsule assembly note the following items Handle the capsule assembly with care and be especially careful not to damage or distort the diaphragms that c...

Page 110: ...transmitter Check correct operating conditions Measurement system problem F0805 ai YES NO NO YES Environmental conditions Operating conditions Transmitter 8 5 2 Troubleshooting Flowcharts YES NO NO Y...

Page 111: ...DRS cable connected properly Check the installation of the impulse piping or process connections and take necessary measure to avoid leakage Are there any pressure leakage observed YES NO YES NO NO YE...

Page 112: ...Amplifier temperature sensor failed AL 02 Amp 1 EEPROM Failure AL 02 Module 1 Amplifier EEPROM failed AL 02 CPU 1 Board Failure AL 02 Module 1 CPU board failed AL 02 1 AL 03 CAP2 ER F Pres 2 Sensor F...

Page 113: ...he variable range For limit values see subsection 3 3 1 AL 12 TEMP1 S Temp 1 outside Limit AL 12 Module 1 Capsule temperature is outside range 50 to 130 degC AL 12 Continues to output the current valu...

Page 114: ...Check the input value 4 AL 36 DP LO N DP Low Alarm AL 36 Differential pressure exceeds the specified lower limit threshold AL 36 AL 37 P1 HI N Pres 1 High Alarm AL 37 Module 1 Input pressure exceeds t...

Page 115: ...J C Pres 1 Zero Trim Err AL 55 Module 1 Specified value is outside of setting range AL 55 Continues to output the current value Adjust so that it is within the specification range 14 Pres 1 Span Trim...

Page 116: ...reach the reference level required to blockage detection AL 88 AL 88 INVR P2 C Invalid Ref Pres 2 AL 88 Module 2 Pressure fluctuation does not reach the reference level required to blockage detection...

Page 117: ...mode for module 1 side pressure AL 91 AL 91 P2 SIM C Pres 2 Simulate Mode AL 91 Under simulation mode for module 2 side pressure AL 91 AL 91 T1 SIM C Temp 1 Simulate Mode AL 91 Under simulation mode...

Page 118: ...current mode is desired but not set in that mode Set in the fixed current mode In multidrop mode Operation is set in the multi drop mode Not write protect mode Operation is set without a password Low...

Page 119: ...corrupt Volatile Memory Defect 0x04 F Not used Watchdog Reset Executed 0x08 F Not used Power Supply Conditions Out of Range 0x10 S Not used Environmental Conditions Out of Range 0x20 S An internal or...

Page 120: ...Good Not Limited Value Hold value Status Bad Low Limited High Limited 1 Temp 1 Sensor Failure AL 01 F Value Measured value Status Poor Accuracy Not Limited Value Measured value Status Bad Not Limited...

Page 121: ...imited 1 Temp 2 Sensor Failure AL 03 F Value Measured value Status Poor Accuracy Not Limited Value Measured value Status Poor Accuracy Not Limited Value Measured value Status Bad Not Limited Cap 2 EEP...

Page 122: ...t Limited AL 12 TEMP1 Temp 1 outside Limit AL 12 Non PV Out of Limits 0x02 S Value Measured value Status Poor Accuracy Not Limited AL 13 AMP TMP Amp T outside Limit AL 13 S Value Measured value Status...

Page 123: ...L 35 DP HI DP High Alarm AL 35 N Value Measured value Status Good Not Limited AL 36 DP LO DP Low Alarm AL 36 N AL 37 P1 HI Pres 1 High Alarm AL 37 N AL 38 P1 LO Pres 1 Low Alarm AL 38 N AL 39 TMP1 HI...

Page 124: ...of other than PV Value Measured value Status Good Not Limited DP Span Trim Err AL 53 C AL 54 P1 RNG Illegal Pres 1 LRV AL 54 C Value Measured value Status Good Not Limited In the case of PV Value Hold...

Page 125: ...Limited In the case of PV Value Measured value Status Poor Accuracy Not Limited In the case of other than PV Value Measured value Status Good Not Limited Pres 2 Span Trim Err AL 57 C Pres 2 Fixed Mode...

Page 126: ...valid Ref DP AL 88 Function Check 0x20 C Value Measured value Status Good Not Limited AL 88 INVR P1 Invalid Ref Pres 1 AL 88 C AL 88 INVR P2 Invalid Ref Pres 2 AL 88 C AL 88 INVR F Invalid Ref BlkF AL...

Page 127: ...us Good Not Limited AL 91 P2 SIM Pres 2 Simulate Mode AL 91 C Value Measured value Status Good Not Limited Value and Status Simulated value Value Measured value Status Good Not Limited AL 91 T1 SIM Te...

Page 128: ...tes the analog channel flag 0x00 R Bi direction mode Bi dir mode Bidirectional mode Sets bidirectional flow mode on or off On Off Off W Burst mode Burst mode Burst mode Switches to or out of burst mod...

Page 129: ...update time for when there are no events and the minimum event retention time M Event Notification Retry Time Event Notification Retry Time Indicates the retry time for when events occur 60 000 s R Ma...

Page 130: ...s diaphragm seal quantity information W Process Conn matl Process Connection material Stores or indicates process Connection material information W Process Conn size Process Connection size Stores or...

Page 131: ...nge value of the user set PV scale As specified W Modify Engr unit User set PV scale value unit Edits the user set PV scale unit string M DP disp point Decimal point of the differential pressure displ...

Page 132: ...m for module 1 side pressure Off Hi Al Detect Lo Al Detect Hi Lo Al Detect Off W Pres 1 Hi alert val High alert value for module 1 side pressure Sets the threshold for the high limit side alarm for mo...

Page 133: ...capsule temperature R Temp 2 Limit Status Device variable limit status Indicates the limit status of the module 2 side capsule temperature R Temp 2 Data Quality Device variable data quality Indicates...

Page 134: ...side zero adjustment point R Pres 1 UTD Module 1 side pressure upper trim deviation Indicates the module 1 side pressure s upper limit side span adjustment level R Pres 1 UTP Module 1 side pressure up...

Page 135: ...e set R Pres 1 Min span Module 1 side minimum span Indicates the minimum span information of the module 1 side pressure R Pres 1 URV Upper range value of module 1 side pressure Sets the upper range va...

Page 136: ...up 18 Hardware status information Indicates module 2 side hardware failure errors R Status group 19 Process status information Indicates module 2 side process errors outside the specification range er...

Page 137: ...unit Sets the module 1 side pressure unit W Pres 2 unit Module 2 side pressure unit Sets the module 2 side pressure unit W Temp unit Temperature unit Sets the temperature unit W Write protection Enab...

Page 138: ...ble DP Pres 1 Pres 2 Temp 1 Temp 2 M SV is SV assignment Indicates the variable currently assigned to SV Pres 1 R Change TV Assgn TV assignment Specifies the variable to assign to TV Teritary variable...

Page 139: ...detecting Pres 2 Side Blocking using BlkF 0 60 W G Lim DPAvgmax DPAvg upper limit threshold Threshold for detection ILDB over Range using DPAvg and Invalid Ref DP using Ref DPAvg 1 00 W G Lim DPAvgmi...

Page 140: ...Ref fP1 A value obtained by comparing the root mean square RSM of the module 1 side pressure fluctuation R G Ratio fP1 Status Status of Ratio fP1 R G BlkF A value obtained by comparing module 1 side p...

Page 141: ...1EN EJX910A Multivariable Transmitter GS 01C25R01 01EN EJX930A Multivariable Transmitter GS 01C25R04 01EN EJXC50A EJXC40A EJAC50E C20FE C20FW C10FR EJXC80A EJAC80E C81FA C82FA C81FD C82FD C30SW C30SE...

Page 142: ...parameters can be verified by reading these parameters from the optional local display or by checking actual calibration of the transmitter The calibration of the transmitter must be performed after...

Page 143: ...ion manual should be followed The personnel performing the repair or replacement of the transmitter should have a sufficient skill level A1 2 7 Startup Time The transmitter generates a valid signal wi...

Page 144: ...achinery plant apparatus under control of the system Basic Safety The equipment must be designed and manufactured such that it protects against risk of damage to persons by electrical shock and other...

Page 145: ...ondition Check that the status of DP is GOOD Check the maximum and minimum values of DP Status Good DP Max Min Max 12 3 kPa Min 12 1 kPa 3 fDP under normal condition Check that the value of fDP is mor...

Page 146: ...DP ILBD over range 8 ILBD parameters Record the values of parameters for ILBD operation Check the status of parameters for ILBD operation Record the value after checked that the status of each paramet...

Page 147: ...ime Diag Period X Diag Supp Count passed Record the value after checked that the status is GOOD fDP 3 74856E 08 fP2 6 23277E 09 fP1 1 51409E 10 BlkF 0 8658873 Record the status of Checkbox in Diag Opt...

Page 148: ...D over range Check that the alarm of Pres 2 Side Blocking is generated Check that the alarm of Pres 1 Side Blocking is not generated Diag Error Pres 2 Side Blocking Pres 1 Side Blocking 9 a 3 Both Sid...

Page 149: ...value is closed Record the values of fDPand fP2 after the certain time Diag Period X Diag Supp Count passed Record the value after checked that the status is GOOD fDP 3 48562E 08 fP2 1 12328E 10 Recor...

Page 150: ...d C30SW and C30SE 3rd Jan 2019 1 2 2 4 2 5 2 9 to 2 11 2 11 2 12 2 13 2 15 4 5 4 8 5 3 to 5 6 10 6 10 25 A1 1 to A1 3 Approved to IEC61508 by Notification body Add notes for keeping the manual and tag...

Reviews: