<9. Parameter Summary>
9-8
IM 01C25W05-01EN
Function
Label
Item
Description
Factory Default
Value
R/W
*1
Signal
characterizer
Num of points
Number of points
Set the number of points for signal
characterizer.(0 to 30)
19
W
Tank memo
Description about the
tank settings
Stores description about the tank settings.
Up to 32 alphanumeric characters
W
X1 to X30
X coordinate
Segment characterizer point
W
Y1 to Y30
Y coordinate
Segment characterizer point
W
X End
X coordinate end point
Segment characterizer end point
100.000%
R
X Start
X coordinate start point
Segment characterizer start point
0.000%
R
X Y initialize
X, Y coordinate
initialization
Set all X,Y in 0%, Divide X,Y into 20 (5%/div)
M
Y End
Y coordinate end point
Segment characterizer end point
100.000%
R
Y Start
Y coordinate start point
Segment characterizer start point
0.000%
R
Pres 1 setup
Pres 1 damp
Module 1 side pressure
damping setting
Sets the module 1 side pressure damping
constant. (0.00 to 100.00 s)
2.00 s
W
Pres 1 LRV
Lower range value of
module 1 side pressure
Sets the lower range value of the module 1
side pressure.
0.000000 MPa
W
Pres 1 LSL
Lower sensor limit of
module 1 side pressure
Indicates the lower limit of the module 1 side
pressure that can be set.
R
Pres 1 Min span
Module 1 side minimum
span
Indicates the minimum span information of
the module 1 side pressure.
R
Pres 1 URV
Upper range value of
module 1 side pressure
Sets the upper range value of the module 1
side pressure.
W
Pres 1 USL
Upper sensor limit of
module 1 side pressure
Indicates the upper limit of the module 1 side
pressure that can be set.
R
Pres 2 setup
Pres 2 damp
Module 2 side pressure
damping setting
Sets the module 2 side pressure damping
constant. (0.00 to 100.00 s)
2.00 s
W
Pres 2 LRV
Lower range value of
module 2 side pressure
Sets the lower range value of the module 2
side pressure.
0.000000 MPa
W
Pres 2 LSL
Lower sensor limit of
module 2 side pressure
Indicates the lower limit of the module 2 side
pressure that can be set.
R
Pres 2 Min span
Module 2 side minimum
span
Indicates the minimum span information of
the module 2 side pressure.
R
Pres 2 URV
Upper range value of
module 2 side pressure
Sets the upper range value of the module 2
side pressure.
W
Pres 2 USL
Upper sensor limit of
module 2 side pressure
Indicates the upper limit of the module 2 side
pressure that can be set.
R
Fixed value
Module 2 side pressure
fixed mode
Sets the module 2 side pressure mode.
(No, Yes, Fall Back)
No
W
Pres 2 fixed val
Module 2 side pressure
fixed value
Sets the fixed value of the module 2 side
pressure.
0.000000 MPa
W
*1:
R:read only, W:read and write, M:method, G:applicable for option code /DG6.