<6. Operation>
6-5
IM 01C25W05-01EN
6.6 Local Parameter Setting
WARNING
The local push button on the integral indicator
must not be used in a hazardous area. When it is
necessary to use the push button, operate it in a
non- hazardous location.
IMPORTANT
• Do not turn off the power to the transmitter
immediately after performing parameter
setting. Powering off within 30 seconds of
performing this procedure will return the
parameter to its previous setting.
• The parameter of Ext SW must be“Enabled”
to perform this configuration. See subsection
7.2.3.11 for the setting procedure.
• LCD update will be slower at low ambient
temperature, and it is recommended to use
LPS function at temperatures above -10°C.
6.6.1 Local Parameter Setting (LPS)
Overview
Parameter configuration by the zero-adjustment
screw and push button (integral indicator code E)
offers easy and quick setup for parameters of Tag
number, Unit, LRV, URV, Damping,Output mode
(linear/square root/signal characterizer), Display out
1, and Re-range by applying actual pressure (LRV/
URV). There is no effect on measurement signal
(analog output or communication signal) when
Local Parameter Setting is carried out.
Zero-adjustment
screw cover
F0607.ai
High pressure side transmitter (master)
Figure 6.7
External Adjustment Screw
F0608.ai
Integral indicator
Push-button
Figure 6.8
Range Setting Switch (push button)