<8. Maintenance>
8-9
IM 01C25W05-01EN
8.5.3 Alarms and Countermeasures
Table 8.3
Errors Message Summary
Indicator
NE107
(Default
Value)
Display on
Configuration
Tool
Cause
Output Operation
during Error
Countermeasure
Status
Group
Diagnostic
List
Group
AL. 01
CAP1.ER
F
Pres 1 Sensor
Failure (AL-01)
Module-1: Pressure
sensor failed. (AL-01)
The output is shifted
to the extreme end
(upper limit or lower
limit) in the direction
set by the burnout
direction switch.
For details on setting
the burnout direction,
see subsection 3.3.9.
Contact the nearest
sales office or service
center.
0
Hardware Failure
Temp 1 Sensor
Failure (AL-01)
Module-1: Capsule
temperature sensor
failed. (AL-01)
Cap 1 EEPROM
Failure (AL-01)
Module-1: Capsule
EEPROM failed. (AL-01)
AL. 02
AMP1.ER
F
Amp T Sensor
Failure (AL-02)
Module-1: Amplifier
temperature sensor
failed. (AL-02)
Amp 1 EEPROM
Failure (AL-02)
Module-1: Amplifier
EEPROM failed. (AL-02)
CPU 1 Board
Failure (AL-02)
Module-1: CPU board
failed. (AL-02)
1
AL.03
CAP2.ER
F
Pres 2 Sensor
Failure (AL-03)
Module-2: Pressure
sensor failed. (AL-03)
18
Temp 2 Sensor
Failure (AL-03)
Module-2: Capsule
temperature sensor
failed. (AL-03)
Cap 2 EEPROM
Failure (AL-03)
Module-2: Capsule
EEPROM failed. (AL-03)
AL.04
AMP2.ER
F
Amp 2 EEPROM
Failure (AL-04)
Module-2: Amplifier
EEPROM failed. (AL-04)
CPU 2 Board
Failure (AL-04)
Module-2: CPU board
failed. (AL-04)
1) Check the cable and
connection.
2) Take measures to
reduce communication
noise.
3) Contact the nearest
sales office or service
center.
AL.05
MDL2.ER
F
Module 2 Failure
(AL-05)
Module-2: Start-up
sequence, power supply
failed. (AL-05)
AL.06
COMM.
ER
F
Intercom Failure
(AL-06)
Module-2: Internal
communication failed.
(AL-06)
—
F
No Device ID
Module-1: No Device ID
is found.
Continues to output
the current value.
Contact the nearest
sales office or service
center.
1