<8. Maintenance>
8-23
IM 01C25W05-01EN
Integral
Indicator
Display
Display on
Configuration
Tool
Device
Status
Extended
Device
Status
NE107
(Default
Value)
Value and Status (Data Quality, Limit Status)
Differential
pressure
Module 1
Module 2
%
Range
Current
Output
Pressure
Capsule
Temperature Pressure
Capsule
Temperature
AL.87
FLG. HI
Flg Temp High
Alarm
(AL-87)
—
Maintenance
Required
(0x01)
M
Value: Measured value
Status: Good, Not Limited
In the case “Off”
is set to Diag Out
Option
Value: Measured
value
Status: Good and
Not Limited
In the case
“Burnout” is set to
Diag Out Option
Value: Low
Limited/High
Limited
Status: Bad and
Low Limited/High
Limited
*1
In the case “Fall
back” is set to
Diag Out Option
Value: Fixed value
Status: Bad and
Constant
AL.87
FLG. LO
Flg Temp Low
Alarm
(AL-87)
M
AL.88
INVR.DP
Invalid Ref DP
(AL-88)
Function Check
(0x20)
C
Value: Measured value
Status: Good, Not Limited
AL.88
INVR.P1
Invalid Ref
Pres 1
(AL-88)
C
AL.88
INVR.P2
Invalid Ref
Pres 2
(AL-88)
C
AL.88
INVR.F
Invalid Ref
BlkF
(AL-88)
C
AL.89
ILBD.OV
ILBD over
Range
(AL-89)
—
N
Value: Measured value
Status: Good, Not Limited
AL.89
B BLK
B Blocking
(AL-89)
Maintenance
Required
(0x01)
M
Value: Measured value
Status: Good, Not Limited
In the case “Off”
is set to Diag Out
Option
Value: Measured
value
Status: Good and
Not Limited
In the case
“Burnout” is set to
Diag Out Option
Value: Low
Limited/High
Limited
Status: Bad and
Low Limited/High
Limited
*1
In the case “Fall
back” is set to
Diag Out Option
Value: Fixed value
Status: Bad and
Constant
AL.89
P1 BLK
Pres 1 Side
Blocking
(AL-89)
M
AL.89
P2 BLK
Pres 2 Side
Blocking
(AL-89)
M
AL.89
P1 LRG
Large Fluct
Pres 1
(AL-89)
M
AL.89
P2 LRG
Large Fluct
Pres 2
(AL-89)
M
AL.89
A BLK
A Blocking
(AL-89)
M
*1: Depends on the setting of hardware switch
*2: Depends on the direction of rangeover (high or low)