<8. Maintenance>
8-12
IM 01C25W05-01EN
Indicator
NE107
(Default
Value)
Display on
Configuration
Tool
Cause
Output Operation
during Error
Countermeasure
Status
Group
Diagnostic
List
Group
AL.50
DP. LRV
C
Illegal DP LRV
(AL-50)
Specified value is
outside of setting range.
(AL-50)
Holds output
immediately before
error occurred.
Check setting and
change them as
needed.
5
Configuration
AL.51
DP. URV
C
Illegal DP URV
(AL-51)
Specified value is
outside of setting range.
(AL-51)
Check setting and
change them as
needed.
AL.52
DP. SPN
C
Illegal DP Span
(AL-52)
Specified value is
outside of setting range.
(AL-52)
Check setting and
change them as
needed.
AL.53
DP. ADJ
C
DP Zero Trim Err
(AL-53)
Specified value is
outside of setting range.
(AL-53)
Continues to output
the current value.
Adjust so that it is
within the specification
range.
DP Span Trim Err
(AL-53)
Specified value is
outside of setting range.
(AL-53)
Adjust so that it is
within the specification
range.
AL.54
P1. RNG
C
Illegal Pres 1 LRV
(AL-54)
Module-1: Specified
value is outside of
setting range. (AL-54)
Holds output
immediately before
error occurred.
Check setting and
change them as
needed.
Illegal Pres 1 URV
(AL-54)
Module-1: Specified
value is outside of
setting range. (AL-54)
Check setting and
change them as
needed.
Illegal Pres 1 Span
(AL-54)
Module-1: Specified
value is outside of
setting range. (AL-54)
Check setting and
change them as
needed.
AL.55
P1. ADJ
C
Pres 1 Zero Trim
Err (AL-55)
Module-1: Specified
value is outside of
setting range. (AL-55)
Continues to output
the current value.
Adjust so that it is
within the specification
range.
14
Pres 1 Span Trim
Err (AL-55)
Module-1: Specified
value is outside of
setting range. (AL-55)
Adjust so that it is
within the specification
range.
AL.56
P2. RNG
C
Illegal Pres 2 LRV
(AL-56)
Module-2: Specified
value is outside of
setting range. (AL-56)
Holds output
immediately before
error occurred.
Check setting and
change them as
needed.
22
Illegal Pres 2 URV
(AL-56)
Module-2: Specified
value is outside of
setting range. (AL-56)
Check setting and
change them as
needed.
Illegal Pres 2 Span
(AL-56)
Module-2: Specified
value is outside of
setting range. (AL-56)
Check setting and
change them as
needed.
AL.57
P2. ADJ
C
Pres 2 Zero Trim
Err (AL-57)
Module-2: Specified
value is outside of
setting range. (AL-57)
Continues to output
the current value.
Adjust so that it is
within the specification
range.
23
Pres 2 Span Trim
Err (AL-57)
Module-2: Specified
value is outside of
setting range. (AL-57)
Adjust so that it is
within the specification
range.
—
C
Pres 2 Fixed Mode
Module-2: Under
pressure and
temperature fix mode.
Continues to output
the current value.
If PV = module 2 side
pressure, 4 mA fixed
output.
Check fixed value
mode.
AL.60
SC. CFG
C
S.C. Config Error
(AL-60)
Set points of signal
characterization do not
increase monotonically.
(AL-60)
Continues to output
the current value.
Check settings and
change them.
14
AL.79
OV.DISP
—
—
Displayed value is
outside the −99999 to
99999 range.
Continues to output
the current value.
Change the setting.
—
—