<8. Maintenance>
8-21
IM 01C25W05-01EN
Integral
Indicator
Display
Display on
Configuration
Tool
Device
Status
Extended
Device
Status
NE107
(Default
Value)
Value and Status (Data Quality, Limit Status)
Differential
pressure
Module 1
Module 2
%
Range
Current
Output
Pressure
Capsule
Temperature Pressure
Capsule
Temperature
AL.50
DP. LRV
Illegal DP LRV
(AL-50)
—
Function Check
(0x20)
C
Value: Measured value
Status: Good, Not Limited
[In the case of PV]
Value: Hold value
Status: Bad,
Constant
[In the case of
other than PV]
Value: Measured
value
Status: Good, Not
Limited
AL.51
DP. URV
Illegal DP URV
(AL-51)
C
AL.52
DP. SPN
Illegal DP
Span
(AL-52)
C
AL.53
DP. ADJ
DP Zero Trim
Err
(AL-53)
C
Value:
Measured
value
Status: Poor
Accuracy |
Not Limited
Value: Measured value
Status: Good, Not Limited
[In the case of PV]
Value: Measured
value
Status: Poor
Accuracy, Not
Limited
[In the case of
other than PV]
Value: Measured
value
Status: Good, Not
Limited
DP Span Trim
Err
(AL-53)
C
AL.54
P1. RNG
Illegal Pres 1
LRV
(AL-54)
C
Value: Measured value
Status: Good, Not Limited
[In the case of PV]
Value: Hold value
Status: Bad,
Constant
[In the case of
other than PV]
Value: Measured
value
Status: Good, Not
Limited
Illegal Pres 1
URV
(AL-54)
C
Illegal Pres 1
Span
(AL-54)
C
AL.55
P1. ADJ
Pres 1 Zero
Trim Err
(AL-55)
C
Value: Measured value
Status: Poor Accuracy,
Not Limited
Value: Measured value
Status: Good, Not Limited
[In the case of PV]
Value: Measured
value
Status: Poor
Accuracy, Not
Limited
[In the case of
other than PV]
Value: Measured
value
Status: Good, Not
Limited
Pres 1 Span
Trim Err
(AL-55)
C
AL.56
P2. RNG
Illegal Pres 2
LRV
(AL-56)
C
Value: Measured value
Status: Good, Not Limited
[In the case of PV]
Value: Hold value
Status: Bad,
Constant
[In the case of
other than PV]
Value: Measured
value
Status: Good, Not
Limited
Illegal Pres 2
URV
(AL-56)
C
Illegal Pres 2
Span
(AL-56)
C
*1: Depends on the setting of hardware switch
*2: Depends on the direction of rangeover (high or low)