<2. Handling Cautions>
2-12
IM 01C25W05-01EN
c. ATEX Intrinsically Safe Type/ATEX
Flameproof Type
EJX/EJA-E Series pressure transmitters with
optional code /KU24 can be selected the type
of protection ATEX Flameproof or Intrinsically
Safe. Ex ia for use in hazardous area.
Note 1. For the installation of this transmitter,
once a particular type of protection is
selected, any other type of protection
cannot be used. The installation must be in
accordance with the description about the
type of protection in this user’s manual.
Note 2. For combined approval types, once a
device of multiple approval type is installed,
it should not be re-installed using any
other approval types. Apply a permanent
mark in the check box of the selected
approval type on the certification label on
the transmitter to distinguish it from unused
approval types.
(2) Electrical Connection
A mark indicating the electrical connection type
is stamped near the electrical connection port.
These marks are as followed.
F0206.ai
Location of the mark
Screw Size
Marking
ISO M20 × 1.5 female
ANSI 1/2 NPT female
M
N or
W
(3) Installation
WARNING
All wiring shall comply with local installation
requirements and the local electrical code.
(4) Operation
WARNING
• OPEN CIRCUIT BEFORE REMOVING
COVER. INSTALL IN ACCORDANCE WITH
THIS USER’S MANUAL
• Take care not to generate mechanical
sparking when access to the instrument and
peripheral devices in a hazardous location.
2.9.3 IECEx Certification
a. IECEx Intrinsic safety
Caution for IECEx Intrinsic safety.
Certification information
Warning:
A modification of the equipment would no
longer comply with the construction described
in the certificate documentation.
Note 1. EJX/EJA-E series pressure transmitters
with optional code /SS24 are applicable for
use in hazardous locations
• No. IECEx FMG 16.0013 X
• Applicable Standard:
IEC 60079-0:2017, IEC 60079-11:2011
• Type of Protection and Marking code:
Ex ia IIC T4 Ga
• Ambient Temperature: –50 °C to +60 °C
• Maximum Process Temperature: 120 °C
• Enclosure: IP66/IP67 in accordance with
only IEC (EN) 60529.
Note 2. Electrical Parameters
• [EJX****-P, EJA****-P]
Supply/Output Circuit (Terminals: +, –)
Ui: 30 V
Ii: 200 mA
Pi: 0.9 W
Ci: 27.6 nF
Li: 0 mH
Communication Circuit (Connector)
Uo: 8.2 V
Io: 160 mA
Po: 0.3 W
Co: 7.6 μF
Lo: 1 mH
• [EJX****-S, EJA****-S]
Ui: 8.2 V
Ii: 200 mA
Pi: 0.4 W
Ci: 6 μF
Li: 0 mH