<4. Installation>
4-8
IM 01C25W05-01EN
4.7 Rotating Transmitter Section
WARNING
For the flameproof type, as a general rule, do not
rotate the transmitter while it is on. If you must do
so, use a gas detector or the like to check that
there is no explosive gas.
The transmitter section can be rotated
approximately 360° and can be fixed at any angle
within the above range. (The direction of the
rotation is depending on the configuration of the
instrument.) Note that there is a stopper which
prevents the transmitter section from being rotated
more than 360°.
1. Using the Allen wrench, loosen the two
setscrews securing the transmitter section to
the capsule assembly.
2. Rotate the transmitter section slowly to the
desired position.
3. Tighten the two setscrews to a torque of 1.5
N·m {15 kgf·cm}.
IMPORTANT
Do not rotate the transmitter section more than
the above limit.
F0413.ai
Setscrew
Transmitter
Stopper
Figure 4.18 Rotating Transmitter Section
4.8 Changing the Direction of
Integral Indicator
IMPORTANT
Always turn OFF power, release pressure and
remove a transmitter to non-hazardous area
before disassembling and reassembling an
indicator.
An integral indicator can be installed in the three
directions. Select the direction that is easy for you
to see. Follow the instructions in section 8.4 for
removing and attaching the integral indicator.
F0414.ai
Figure 4.19 Integral Indicator Direction