<8. Maintenance>
8-13
IM 01C25W05-01EN
Indicator
NE107
(Default
Value)
Display on
Configuration
Tool
Cause
Output Operation
during Error
Countermeasure
Status
Group
Diagnostic
List
Group
AL.87
FLG. HI
M
Flg Temp High
Alarm (AL-87)
Module-1: Flange
temperature exceeds
the specified upper limit
threshold. (AL87)
Follows the Diag Out
Option settings.
Off:
Continues to output
the current value.
Burnout:
Shifts the output to
the AO upper limit
or AO lower limit
parameter value.
Fall back:
Outputs the value
specified by the
Diag Fixed Out Val
parameter.
1) Check heater
malfunction and
disconnection.
2) Check the capsule
temp. and amplifier
temp.
3) Adjust flange
temperature
coefficient(Flg temp
coef).
15
Transducer Status
AL.87
FLG. LO
M
Flg Temp Low
Alarm (AL-87)
Module-1: Flange
temperature exceeds
the specified lower limit
threshold. (AL87)
AL.88
INVR.DP
C
Invalid Ref DP
(AL-88)
Differential pressure
fluctuation does not
reach the reference level
required to blockage
detection so that no
blockage detection is
carried out.(AL-88)
Continues to output
the current value.
1) Check process
condition.
2) Obtain the reference
fluctuation values
again.
15
AL.88
INVR.P1
C
Invalid Ref Pres 1
(AL-88)
Module-1: Pressure
fluctuation does not
reach the reference level
required to blockage
detection. (AL-88)
AL.88
INVR.P2
C
Invalid Ref Pres 2
(AL-88)
Module-2: Pressure
fluctuation does not
reach the reference level
required to blockage
detection. (AL-88)
AL.88
INVR.F
C
Invalid Ref BlkF
(AL-88)
Blocking factor can not
be used for blockage
detection.(AL-88)
AL.89
ILBD.OV
N
ILBD over Range
(AL-89)
Process value is outside
the applicable range of
blockage diagnostics.
(AL-89)
Check the process
conditions.
15
AL.89
B BLK
M
B Blocking
(AL-89)
B blocking (both-side
blockage) has been
detected. (AL-89)
Follows the Diag Out
Option settings.
Off:
Continues to output
the current value.
Burnout:
Shifts the output to
the AO upper limit
or AO lower limit
parameter value.
Fall back:
Outputs the value
specified by the
Diag Fixed Out Val
parameter.
1) Check the process
and impulse line
conditions.
2) If there are large
flow change or the
change of fluid under
the measured process
conditions, obtain the
reference value again.
16
AL.89
P1 BLK
M
Pres 1 Side
Blocking (AL-89)
Module 1 side blockage
has been detected.
(AL-89)
AL.89
P2 BLK
M
Pres 2 Side
Blocking (AL-89)
Module 2 side blockage
has been detected.
(AL-89)
AL.89
P1 LRG
M
Large Fluct Pres 1
(AL-89)
Module-1: Pressure
fluctuation amplitude is
large. (AL-89)
AL.89
P2 LRG
M
Large Fluct Pres 2
(AL-89)
Module-2: Pressure
fluctuation amplitude is
large. (AL-89)
AL.89
A BLK
M
A Blocking
(AL-89)
A blocking (one-side
blockage) has been
detected. (AL-89)