<4. Installation>
4-3
IM 01C25W05-01EN
F0415.ai
*: The customer should prepare
the mating gasket and clamp,
They are also available from
Yokogawa; if required, please
order them separately. Refer to
Table 4.2.
Tank
Sleeve
Gasket* (Optional)
Clamp* (Optional)
Figure 4.6
Mounting Hygienic Seals (Flush Type)
(Hygienic, flush type)
F0416.ai
*: The customer should prepare the
mating O-ring, clamp, and tank
spud. They are also available
from Yokogawa; if required,
please order them separately.
Refer to Table 4.1 and 4.2.
Tank
Tank spud*
(sold separately)
O-ring* (Optional)
Clamp* (Optional)
Figure 4.7
Mounting Hygienic Seals
(Extended Type)
IMPORTANT
• When measuring the liquid level of the tank,
the minimum liquid level (zero point) must
be set to a level at least 50 mm above the
center of the high pressure side diaphragm
seal (see Figure 4.9).
• Correctly install the diaphragm seal part on
the tank, checking the label “PRESSURE
HIGH” or “PRESSURE LOW” on each seal.
• Exercise care so as not to damage
diaphragm surfaces. For models with
diaphragm seals, since the diaphragm
protrudes approx. 1 mm from the flange
surface, do not place the pressure detector
section face down on a surface as this can
damage the diaphragm.
• Fix the DRS cable in place to keep it from
moving due to wind or vibration. If the DRS
cable is too long, loosely coil the extra tube
portion (coil diameter of 250 mm or more)
and secure the coiled tube with a clamp.
F0406.ai
Serial number and product model
Serial number and product model
Tag number
PRESSURE HIGH
PRESSURE LOW
Figure 4.8
Master/Slave Nameplate Description
50 mm or more
Minimum liquid level
Low pressure
side transmitter
(slave)
High pressure
side transmitter
(master)
F0407.ai
Fix the DRS cable in place
so that tension is not
applied to the connector.
WARNING
Figure 4.9
Example of Mounting to a Tank