<9. Parameter Summary>
9-5
IM 01C25W05-01EN
Function
Label
Item
Description
Factory Default
Value
R/W
*1
Loop test
Loop test
Test output
Outputs a 4-20 mA test signal. Set in unit of
mA. (3.8 to 21.6 mA)
M
Test Auto Release
Time
Auto test release time
Sets the auto release time for loop test,
device variable simulation and status
simulation. (10 min, 30 min, 60 min, 3 hour, 6
hour, 12 hour)
10 min
W
Low cut
Low cut
Low-cut value setting
Indicates or sets the low-cut reference value
for the output. (0.00 to 20.00%)
10.00%
W
Low cut mode
Low cut mode
Set the output operation for low cut.
(Linear, Zero)
Linear
W
Number of
preambles
Num req preams
Number of requested
preambles
Indicates the number of requested
preambles of HART communication.
5
R
Num resp preams Number of response
preambles
Indicates the number of response
preambles.
5
R
Impulse line
connection
orientation
swap
Pres 1/2 Swap
Pres 1/2 swap
Selects the software input Pres 1/Pres 2
swap function. (Normal, Reverse)
Normal
W
Polling
address
Poll addr
Polling address
Indicates or sets the polling address for
multidrop connection. (0 to 63)
0
W
Loop current mode Loop current mode
Sets current output to fixed or variable in
multidrop connection. (Disabled, Enabled)
Disabled
W
Process alerts DP alert mode
Hi/Lo alert mode for
differential pressure
Sets the operation mode of the Hi/Lo alarm
for differential pressure. (Off, Hi. Al Detect,
Lo. Al Detect, Hi/Lo. Al Detect)
Off
W
DP Hi alert val
High alert value for
differential pressure
Set the threshold for the high limit side alarm
for differential pressure.
W
DP Lo alert val
Low alert value for
differential pressure
Set the threshold for the low limit side alarm
for differential pressure.
W
Pres 1 alert mode
Hi/Lo alert mode for
module 1 side pressure
Sets the operation mode of the Hi/Lo alarm
for module 1 side pressure. (Off, Hi. Al
Detect, Lo. Al Detect, Hi/Lo. Al Detect)
Off
W
Pres 1 Hi alert val High alert value for
module 1 side pressure
Sets the threshold for the high limit side
alarm for module 1 side pressure.
W
Pres 1 Lo alert val Low alert value for
module 1 side pressure
Sets the threshold for the low limit side alarm
for module 1 side pressure.
W
Pres 2 alert mode
Hi/Lo alert mode for
module 2 side pressure
Sets the operation mode of the Hi/Lo alarm
for module 2 side pressure. (Off, Hi. Al
Detect, Lo. Al Detect, Hi/Lo. Al Detect)
Off
W
Pres 2 Hi alert val High alert value for
module 2 side pressure
Sets the threshold for the high limit side
alarm for module 2 side pressure.
W
Pres 2 Lo alert val Low alert value for
module 2 side pressure
Sets the threshold for the low limit side alarm
for module 2 side pressure.
W
Temp 1 alert mode
Hi/Lo alert mode for
module 1 capsule
temperature
Sets the operation mode of the Hi/Lo alarm
for module 1 side capsule temperature. (Off,
Hi. Al Detect, Lo. Al Detect, Hi/Lo. Al Detect)
Off
W
Temp 1 Hi alert val High alert value for
module 1 side capsule
temperature
Sets the threshold for the high limit
side alarm for module 1 side capsule
temperature.
120°C
W
Temp 1 Lo alert val Low alert value for
module 1 side capsule
temperature
Sets the threshold for the low limit side alarm
for module 1 side capsule temperature.
–40°C
W
Temp 2 alert mode
Hi/Lo alert mode for
module 2 capsule
temperature
Sets the operation mode of the Hi/Lo alarm
for module 2 side capsule temperature. (Off,
Hi. Al Detect, Lo. Al Detect, Hi/Lo. Al Detect)
Off
W
Temp 2 Hi alert val High alert value for
module 2 side capsule
temperature
Sets the threshold for the high limit
side alarm for module 2 side capsule
temperature.
120°C
W
Temp 2 Lo alert val Low alert value for
module 2 side capsule
temperature
Sets the threshold for the low limit side alarm
for module 2 side capsule temperature.
–40°C
W
*1:
R:read only, W:read and write, M:method, G:applicable for option code /DG6.