9 Fully-closed Control
9.2.2 Analog Signal Input Timing
9-4
9.2.2 Analog Signal Input Timing
The following figure shows the input timing of the analog signals.
When the cos and sin signals are shifted 180 degrees, the differential signals are the /cos and /sin signals. The
specifications of the cos, /cos, sin, and /sin signals are identical except for the phase.
Input the signals Ref and /Ref so that they shall cross each other as shown in the figure because they are input
into the converter. When they are crossed, the output data will be counted up.
Precautions
1. Never perform insulation resistance and withstand voltage tests.
2. When analog signals are input to the serial converter unit, noise influence on the analog signals affects
the unit’s ability to output correct position information. The analog cable must be as short as possible
and shielded.
3. Do not connect or disconnect the unit while power is being supplied, or the unit may be damaged.
4. When using multiple axes, use a shield cable for each axis. Do not use a shield cable for multiple axes.
Zero Point
Count up direction
5 to 75%
45
100%
cos
/cos
cos /cos sin /sin
Input voltage range:
1.5 V to 3.5V
Ref /Ref
Input voltage range:
1.5 V to 3.5V
sin
/sin
Ref
/Ref
0.2 to 0.6
0.2V min.
0.2V min.
5 to 75%
IMPORTANT
Summary of Contents for SGDS Sigma III Series
Page 3: ...SGDS Sigma III Servo Amplifier User Manual for Mechatrolink II Communications...
Page 21: ......
Page 59: ...2 System Selection 2 5 4 Regenerative Resistors 2 28...
Page 68: ...3 3 SERVOPACK Internal Block Diagrams 3 9 3 3 3 Three phase 200 V 1 0 kW...
Page 82: ...3 7 Dimensional Drawings of Base mounted SERVOPACK Model SGDS 12A 12A 3 23 Three phase 1 5kW...
Page 133: ...5 Wiring 5 7 2 Connecting Externally Regenerative Resistors 5 28...
Page 229: ...7 Operation 7 7 4 Absolute Encoder Home Position Offset 7 38...