5 Wiring
5.3.2 I/O Signal Connector (CN1) Terminal Layout
5-10
5.3.2 I/O Signal Connector (CN1) Terminal Layout
The following diagram shows the layout of the CN1 terminals.
* 1. Make the signal allocations using parameters.
* 2. Connect a battery to CN1 or to a battery case. Connecting both batteries creates a loop circuit that is
dangerous between the two batteries.
Note: 1. The connector shell is connected to the FG (frame ground)
2. Do not use the unused terminals.
5.3.3 I/O Signal (CN1) Names and Functions
(1) Input Signals
Note: 1. The functions allocated to /DEC, P-OT, N-OT, /EXT1, /EXT2, and /EXT3 input signals can be
changed by setting the parameters.
2. For forward/reverse run prohibited, the SERVOPACK processing for stopping is executed by the
software. As the safety specifications of some applications may not satisfy local safety require-
ments, add the external safety circuits as required.
3. The signal /SI0 (pin No. 13) can be monitored as a general-purpose input with the
MECHATROLINK/MECHATROLINK II.
1
3
5
7
9
11
13
2
4
6
8
10
12
14
16
18
20
22
24
26
15
17
19
21
23
25
/BK+
(/SO1+)
Brake interlock
output
Servo alarm
output
Forward run
prohibited input
External latch
signal 2 input
External latch
signal 1 input
External latch
signal 3 input
General-purpose
input
General-purpose
input
General-purpose
input
General-purpose
input
General-purpose
input
Zero-point return
deceleration
switch input
Reverse run
prohibited input
Servo alarm
output
Control power
supply for sequence
signal input
Brake interlock
output
Battery (+)
input
Battery (-)
input
Signal ground
PG dividing
pulse (Phase-A)
output
PG dividing
pulse (Phase-A)
output
PG dividing
pulse (Phase-B)
output
PG dividing
pulse (Phase-C)
output
PG dividing
pulse (Phase-B)
output
PG dividing
pulse (Phase-C)
output
P-OT
(/SI1)
/DEC
(/SI3)
/EXT2
(/SI5)
/SI0
ALM+
/BK-
(/SO1-)
N-OT
(/SI2)
/EXT1
(/SI4)
/EXT3
(/SI6)
ALM-
+24VIN
BAT(+)
∗
2
SG
/PAO
/PBO
/PCO
/SO2-
∗
1
/SO3-
∗
1
BAT(-)
∗
2
PAO
PBO
PCO
/SO2+
∗
1
/SO3+
∗
1
Signal Name
Pin No.
Function
Com-
mon
/DEC
9
Homing deceleration limit switch signal:
Connects the deceleration LS (limit switch) for homing.
P-OT
N-OT
7
8
Forward run prohibited signal
Reverse run prohibited signal
Overtravel prevention signal:
Stops servomotor when movable part travels
beyond the allowable range of motion.
/EXT1toEXT3
/EXT2
/EXT3
10
11
12
External latch signals 1, 2, and 3:
Connects the external signals that latch the current FB pulse counter.
+24VIN
6
Control power supply for sequence signal:
Users must p24 V power supply. Allowable voltage fluctuation
range: +11 to +25 V
BAT (+)
BAT (-)
14
15
Battery input for absolute encoder:
Used for absolute encoder battery input when a battery unit is not used.
/SI0
13
General-purpose sequence input signal:
Monitored in the I/O monitor field of MECHATROLINK/MECHATROLINK
II.
Summary of Contents for SGDS Sigma III Series
Page 3: ...SGDS Sigma III Servo Amplifier User Manual for Mechatrolink II Communications...
Page 21: ......
Page 59: ...2 System Selection 2 5 4 Regenerative Resistors 2 28...
Page 68: ...3 3 SERVOPACK Internal Block Diagrams 3 9 3 3 3 Three phase 200 V 1 0 kW...
Page 82: ...3 7 Dimensional Drawings of Base mounted SERVOPACK Model SGDS 12A 12A 3 23 Three phase 1 5kW...
Page 133: ...5 Wiring 5 7 2 Connecting Externally Regenerative Resistors 5 28...
Page 229: ...7 Operation 7 7 4 Absolute Encoder Home Position Offset 7 38...