8 Adjustments
8.6.8 Less Deviation Control
8-40
8.6.8 Less Deviation Control
Less Deviation Control can provide shorter settling times and lower locus tracking errors by reducing the
position error as much as possible for the position control mode. There are two kinds of Less deviation control:
Basic Less deviation and Less Deviation control with reference filter. Operation can be adjusted easily with
utility function Fn015 (One-parameter Tuning for Less Deviation Control.) If higher performance operation is
required, the settings can be fine-tuned with the parameters.
Example Response Waveforms for Less Deviation Control
(1) Related Parameters
Example Response Waveform
for Less Deviation Control
Example Response Waveform
for Less Deviation Control with Reference Filter
Position
Position
Error
Time
Time
Position reference
(Host reference)
Using Less Deviation
Control
Using Less
Deviation Control
Not using Less
Deviation Control
Not using Less
Deviation Control
Position
Position
Error
Time
Time
Position reference
(Host reference)
Using Less Deviation Control
with Reference filter
Using Less Deviation Control
with Reference filter
Not using Less Deviation Control
with Reference Filter
Not using
Less Deviation Control
Pn119
Reference Filter Gain
Setting Range
Setting Unit
Factory Setting
Setting Validation
1.0 to 2,000.0 /s
0.1 /s
50.0 /s
Immediately
Pn11A
Reference Filter Gain Compensation
Setting Range
Setting Unit
Factory Setting
Setting Validation
50.0% to 200.0%
0.1%
100%
Immediately
Pn11E
Reference Filter Bias (Forward)
Setting Range
Setting Unit
Factory Setting
Setting Validation
0.0% to 1,000.0%
0.1%
100%
Immediately
Pn144
Reference Filter Bias (Reverse)
Setting Range
Setting Unit
Factory Setting
Setting Validation
0.0% to 1,000.0%
0.1%
100%
Immediately
Pn1A0
Servo Rigidity
Setting Range
Setting Unit
Factory Setting
Setting Validation
1% to 500%
1%
60%
Immediately
Pn1A1
Servo Rigidity #2
Setting Range
Setting Unit
Factory Setting
Setting Validation
1% to 500%
1%
60%
Immediately
Position
Position
Position
Position
Position
Position
Summary of Contents for SGDS Sigma III Series
Page 3: ...SGDS Sigma III Servo Amplifier User Manual for Mechatrolink II Communications...
Page 21: ......
Page 59: ...2 System Selection 2 5 4 Regenerative Resistors 2 28...
Page 68: ...3 3 SERVOPACK Internal Block Diagrams 3 9 3 3 3 Three phase 200 V 1 0 kW...
Page 82: ...3 7 Dimensional Drawings of Base mounted SERVOPACK Model SGDS 12A 12A 3 23 Three phase 1 5kW...
Page 133: ...5 Wiring 5 7 2 Connecting Externally Regenerative Resistors 5 28...
Page 229: ...7 Operation 7 7 4 Absolute Encoder Home Position Offset 7 38...