7 Operation
7.7.3 Multi-turn Limit Setting
7-36
Change the setting using the following procedure.
1. Change the multi-turn limit setting (Pn205), and then turn OFF the SERVOPACK control power and turn
it ON again. The alarm A.CC0 occurs. The multi-turn limit value for the encoder is setting 65535, the
same as for the SERVOPACK’s factory setting. Therefore, if only the multi-turn limit value for the SER-
VOPACK is changed, the alarm occurs.
Alarm Name: Multi-turn Limit Disagreement
2. The multi-turn limit value for the encoder must be set to the same value as that for the SERVOPACK.
Change the multi-turn limit value for the encoder using the following procedure.
Use a digital operator for the following operation. This operation is enabled only while the alarm A.CC0
occurs.
• Refer to
11.3.3 Multi-turn Limit Setting
for details about how to use the adjusting command
(ADJ: 3EH).
The multi-turn limit setting in the encoder can be changed only while the Multi-turn Limit Disagreement (A.CC0) has
occurred. The setting is enabled by turning OFF the control power and turning it ON again.
Alarm Display
Explanation
A.CC0
The multi-turn limit values for the encoder and SERVOPACK are different.
A . C C 0
- F U N C T I O N -
F n 0 1 2
F n 0 1 3
F n 0 1 6
F n 0 1 7
A . C C 0
M u l t i t u r n L i m i t
S e t
S t a r t : [ D A T A ]
R e t u r n : [ S E T ]
D o n e
M u l t i t u r n L i m i t
S e t
S t a r t : [ D A T A ]
R e t u r n : [ S E T ]
Operation Key
Description
Display
Open the Utility Function Mode main menu and select
Fn013.
Turn OFF the power, and then turn it ON again to make the setting valid.
Press the Key.
The display is switched to the setting display of Fn013
(Multi-turn Limit Value Setting Change When a Multi-
turn Limit Disagreement Alarm (A.CC0) Occurs).
Note: If the display is not switched and "NO-OP" is displayed
in the status display, the Write Prohibited Setting
(Fn010 = 0001) i s set. Check the setting and reset.
Press the Key to set the multi-turn limit value.
When the setting is completed, "Done" is displayed in the
status display. Turn the power Off then ON to update the
multi-turn limit setting.
Note: Press the Key not to set the value. The display
returns to the Utility Function Mode main menu.
INFO
Summary of Contents for SGDS Sigma III Series
Page 3: ...SGDS Sigma III Servo Amplifier User Manual for Mechatrolink II Communications...
Page 21: ......
Page 59: ...2 System Selection 2 5 4 Regenerative Resistors 2 28...
Page 68: ...3 3 SERVOPACK Internal Block Diagrams 3 9 3 3 3 Three phase 200 V 1 0 kW...
Page 82: ...3 7 Dimensional Drawings of Base mounted SERVOPACK Model SGDS 12A 12A 3 23 Three phase 1 5kW...
Page 133: ...5 Wiring 5 7 2 Connecting Externally Regenerative Resistors 5 28...
Page 229: ...7 Operation 7 7 4 Absolute Encoder Home Position Offset 7 38...