YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
775
■
n4-63: Speed EstimateResponse@High Freq
No.
(Hex.)
Name
Description
Default
(Range)
n4-63
(1B83)
Speed
EstimateResponse@High
Freq
In high speed ranges, where the output frequency is ≥
n4-67 [SwitchingFreq forEstimation gain]
,
this adjusts the responsiveness of the speed estimation.
60.0
(0.1 - 300.0)
When an improvement in the response of speed estimation is desired, or when the motor speed oscillates, or when
there is a significant amount of torque ripple, increase the setting value in 10.0 increments. If no improvement is
obtained, decrease the setting value in 10.0 increments.
Note:
Before adjusting
n4-63, n4-64 [Speed Estimate Response@Low Freq], n4-65 [Flux Estimate Response@High Freq], n4-66 [Flux
Estimate Response @Low Freq]
, carry out rotational Auto-Tuning.
■
n4-64: Speed Estimate Response@Low Freq
No.
(Hex.)
Name
Description
Default
(Range)
n4-64
(1B84)
Speed Estimate
Response@Low Freq
In low speed ranges, where 0 ≤ the output frequency, which is <
n4-67 [SwitchingFreq
forEstimation gain]
, this adjusts the responsiveness of the speed estimation.
60.0
(0.1 - 300.0)
When an improvement in the response of speed estimation is desired, or when the motor speed oscillates, or when
there is a significant amount of torque ripple, increase the setting value in 10.0 increments. If no improvement is
obtained, decrease the setting value in 10.0 increments.
Note:
Before adjusting
n4-63 [Speed EstimateResponse@High Freq]
,
n4-64
,
n4-65 [Flux Estimate Response@High Freq]
,
n4-66 [Flux
Estimate Response @Low Freq]
, carry out rotational Auto-Tuning.
■
n4-65: Flux Estimate Response@High Freq
No.
(Hex.)
Name
Description
Default
(Range)
n4-65
(1B85)
Flux Estimate
Response@High Freq
In high speed ranges, where the output frequency is ≥
n4-67 [SwitchingFreq forEstimation gain]
,
this adjusts the responsiveness of the magnetic flux estimation. Usually it is not necessary to
change this setting.
1.00
(0.50 - 3.00)
If, under no-load conditions,
oS [Overspeed]
is detected, or if for any other reason the speed does not stabilize
within the high speed range, adjust the setting value up or down in increments of 0.05.
■
n4-66: Flux Estimate Response @Low Freq
No.
(Hex.)
Name
Description
Default
(Range)
n4-66
(1B86)
Flux Estimate Response
@Low Freq
Sets the responsiveness of the magnetic flux estimation in low speed ranges, where 0 ≤ the output
frequency, which is <
n4-67 [Estimate Gain Switchover Freq]
. Usually it is not necessary to
change this setting.
1.50
(0.50 - 3.00)
if, under no-load conditions,
oS [Overspeed]
is detected, or if for any other reason the speed does not stabilize
within the low speed range, adjust the setting value up or down in increments of 0.05.
■
n4-67: Estimate Gain Switchover Freq
No.
(Hex.)
Name
Description
Default
(Range)
n4-67
(1B87)
Estimate Gain Switchover
Freq
Set the switching frequency for estimation gain for each of the following:
n4-63
[SpdEstimationResponseForHighFreq]
,
n4-64 [SpdEstimationResponse forLowFreq]
,
n4-65
[FluxEstimationResponseForHighFrq]
, and
n4-66 [FluxEstimationResponseForLowFreq]
.
Usually it is not necessary to change this setting.
6.00 Hz
(0.00 - E1-04)
If the output frequency is greater than
n4-67
,
n4-63
and
n4-65
are selected. If the output frequency is less than
n4-
67
,
n4-64
and
n4-66
are selected.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Summary of Contents for CR700
Page 1: ......
Page 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...