
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
629
This parameter does not change the lower limit of Jog reference, frequency reference for multi-step speed
operation, or the auxiliary frequency reference.
The drive operates at the value set in
d2-03
when the frequency reference decreases to less than the value set in
d2-03
.
Note:
When lower limits are set to parameters
d2-02 [Frequency Reference Lower Limit]
and
d2-03
, the drive uses the larger value as the
lower limit.
◆
d3: Jump Frequency
The Jump frequency is a function that sets the dead band to a specified frequency band. If a machine that operated
at constant speed is operated with variable speed, it can make resonance. To operate the machine without
resonance from the natural frequency of the machinery mechanical system, use a frequency band jump.
You can program the drive to have three different Jump frequencies. Sets
d3-01[Jump Frequency 1]
to
d3-03
[Jump Frequency 3]
to the center value for the frequency to avoid and sets
d3-04 [Jump Frequency Width]
to be
1/2 of the total band to avoid.
When you input a frequency reference that is the same as or near the Jump frequency width, the frequency
reference changes automatically.
The drive accelerates or decelerates the motor smoothly until the frequency reference is not in the range of the
Jump frequency band. The drive will use the active accel/decel time to go through the specified dead band range.
If the frequency reference is not in the range of the Jump frequency band, switch to constant speed operation.
Figure 11.44 Jump Frequency
Note:
•
When you set Jump Frequencies 1 to 3, make sure that the parameters do not overlap. The drive will not indicate this condition.
•
When the drive is in the range of the Jump frequency, the frequency reference changes automatically. When the drive jumps
frequencies, the output frequency changes smoothly as specified by the values set in
C1-01 [Acceleration Time 1]
and
C1-02
[Deceleration Time 1]
.
■
d3-01: Jump Frequency 1
No.
(Hex.)
Name
Description
Default
(Range)
d3-01
(0294)
Jump Frequency 1
Sets the median value of the frequency band that the drive will avoid.
0.0 Hz
(Determined by A1-02)
Note:
Set this parameter to 0.0 Hz to disable the Jump frequency.
■
d3-02: Jump Frequency 2
No.
(Hex.)
Name
Description
Default
(Range)
d3-02
(0295)
Jump Frequency 2
Sets the median value of the frequency band that the drive will avoid.
0.0 Hz
(Determined by A1-02)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Summary of Contents for CR700
Page 1: ......
Page 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Page 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...