Figure 11.58 Example MFDO when Set for Watt Hours
Note:
•
Watt hours are not counted when the power value is a negative value (regenerative state).
•
Stores the Watt hours while the control power supply to the drive is operating. The Watt hour count is reset when the control power is
cut because of a momentary power loss or other reason.
0 : 0.1 kWh units
1 : 1 kWh units
2 : 10 kWh units
3 : 100 kWh units
4 : 1000 kWh units
■
H2-07: Modbus Register 1 Address Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-07
(0B3A)
Modbus Register 1 Address
Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
Sets
H2-07
with the address of the register that is output to
Modbus Reg 1 Status Satisfied [H2-01 to H2-05 = 62]
and sets
H2-08
with the bit value.
■
H2-08: Modbus Register 1 Bit Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-08
(0B3B)
Modbus Register 1 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
Sets
H2-07
with the address of the register that is output to
Modbus Reg 1 Status Satisfied [H2-01 to H2-05 = 62]
and sets
H2-08
with the bit value.
■
H2-09: Modbus Register 2 Address Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-09
(0B3C)
Modbus Register 2 Address
Select
Sets the address of the MEMOBUS/Modbus register output to the MFDO terminal.
0001
(0001 - 1FFF)
Sets
H2-09
with the address of the register that is output to
Modbus Reg 2 Status Satisfied [H2-01 to H2-05 = 63]
and sets
H2-10
with the bit value.
■
H2-10: Modbus Register 2 Bit Select
No.
(Hex.)
Name
Description
Default
(Range)
H2-10
(0B3D)
Modbus Register 2 Bit
Select
Sets the bit of the MEMOBUS/Modbus register output to the MFDO terminal.
0000
(0000 - FFFF)
Sets
H2-09
with the address of the register that is output to
Modbus Reg 2 Status Satisfied [H2-01 to H2-05 = 63]
and sets
H2-10
with the bit value.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Summary of Contents for CR700
Page 1: ......
Page 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Page 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...