11.2 A: Initialization Parameters
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
575
No.
Name
Optimal Value
d1-02
Reference 2
25.00 Hz
d1-03
Reference 3
50.00 Hz
H1-05
Terminal S5 Function Selection
3: Multi-Step Speed Reference 1
H1-06
Terminal S6 Function Selection
4: Multi-Step Speed Reference 2
H2-01
Term M1-M2 Function Selection
0: During Run
H2-02
Term M3-M4 Function Selection
37: During Frequency Output
H3-06
Terminal A3 Function Selection
F: Not Used (Through Mode)
L3-04
Stall Prevention during Decel
0: Disabled
L8-05
Input Phase Loss Protection Sel
1: Enabled
L8-07
Output Phase Loss Protection Sel
1: Fault when One Phase is Lost
L8-38
Carrier Frequency Reduction
1: Enabled below 6 Hz
L8-41
High Current Alarm Selection
1: Enabled
S1-01
Brake Release Frequency (FWD)
0.0 Hz
S1-02
Brake Release Frequency (REV)
0.0 Hz
S1-03
Brake Delay Frequency
0.0 Hz
S1-04
Brake Delay Time
0.00 s
S1-12
Brake Hold Frequency (FWD)
0.0 Hz
S1-13
Brake Hold Frequency (REV)
0.0 Hz
S1-14
Slip Prevention Frequency
0.0 Hz
S1-15
Slip Prevention Time
0.00 s
S1-16
Sequence Fault SE1 Detect Time
0.00 s
S1-17
Sequence Fault SE2 Detect Time
0.00 s
S1-18
Sequence Fault SE3 Detect Time
0.00 s
S1-19
Sequence Fault SE4 Detect Time
0.00 s
S1-54
Brake Sequence Selection
0: Disabled
The drive saves these parameters as user parameters.
Table 11.5 Parameters Saved as User Parameters with the Traveling Preset
User Parameter No.
Parameter No. Saved
Name
A2-01
b1-01
Frequency Reference Selection 1
A2-02
C1-01
Acceleration Time 1
A2-03
C1-02
Deceleration Time 1
A2-04
d1-01
Reference 1
A2-05
d1-02
Reference 2
A2-06
d1-03
Reference 3
A2-07
E2-01
Motor Rated Current (FLA)
A2-08
H1-05
Terminal S5 Function Selection
A2-09
H1-06
Terminal S6 Function Selection
A2-10
H2-01
Term M1-M2 Function Selection
A2-11
L1-01
Motor Overload (oL1) Protection
3 : Closed Loop Crane (Hoist)
The drive automatically sets these parameters for a closed loop crane (hoist) application.
Table 11.6 Optimal Settings for Closed Loop Crane (Hoist) Applications
No.
Name
Optimal Value
A1-02
Control Method Selection
3: Closed Loop Vector (CLV)
b1-01
Frequency Reference Selection 1
0: Keypad
Summary of Contents for CR700
Page 1: ......
Page 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Page 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...