SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
737
The analog signal output from the terminal AM is a maximum of ±10 V. Select the signal level with
H4-08
[Terminal AM Signal Level Select]
.
Examples of possible settings:
When the output current of a monitoring item is 100% (drive rated current) in these examples, the voltage of AM
terminal outputs at 5 V (50% of 10 V). Subsequently, the output current at the time the AM terminal outputs a
maximum voltage of 10 V will be 200% of the drive rated current.
•
H4-04 = 103 [Terminal AM Analog Output Select = Output Current]
•
H4-05 = 50.0%
•
H4-06 = 0.0% [Terminal AM Analog Output Bias = 0.0%]
•
H4-08 = 0 [0 to 10 Vdc]
■
H4-06: Terminal AM Analog Output Bias
No.
(Hex.)
Name
Description
Default
(Range)
H4-06
(0422)
RUN
Terminal AM Analog
Output Bias
Sets the bias of the
Ux-xx
monitor signal set in
H4-04 [terminals AM Monitor Selection]
.
0.0%
(-999.9 - +999.9%)
The analog signal output from the terminal AM is a maximum of ±10 V. Select the signal level with
H4-08
[Terminal AM Signal Level Select]
.
■
H4-07: Terminal FM Signal Level Select
No.
(Hex.)
Name
Description
Default
(Range)
H4-07
(0423)
Terminal FM Signal Level
Select
Sets the MFAO terminal FM output signal level.
0
(0, 1)
0 : 0 to 10 Vdc
1 : -10 to +10 Vdc
■
H4-08: Terminal AM Signal Level Select
No.
(Hex.)
Name
Description
Default
(Range)
H4-08
(0424)
Terminal AM Signal Level
Select
Sets the MFAO terminal AM output signal level.
0
(0, 1)
0 : 0 to 10 Vdc
1 : -10 to +10 Vdc
■
H4-20: Analog Power Monitor 100% Level
No.
(Hex.)
Name
Description
Default
(Range)
H4-20
(0B53)
Analog Power Monitor
100% Level
Sets the level at 10 V when
U1-08 [Output Power]
is set for analog output.
0.00 kW
(0.00 - 650.00 kW)
Note:
When
H4-20 = 0.00 kW
, the output power monitor 10 V level is determined by
E2-11 [Motor Rated Power (kW)]
.
◆
H5: Memobus/Modbus Communication
H5 parameters
configure the drive to use MEMOBUS/Modbus communications.
You can use the MEMOBUS/Modbus protocol over the RS-485 port (terminals D+ and D-) in the drive to use
serial communication with programmable controllers (PLC).
■
H5-01: Drive Node Address
No.
(Hex.)
Name
Description
Default
(Range)
H5-01
(0425)
Drive Node Address
Sets the communication slave address for drives.
1FH
(0 - FFH)
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
Summary of Contents for CR700
Page 1: ......
Page 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Page 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...