11.2 A: Initialization Parameters
YASKAWA
SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
571
2. Set
o2-03 = 1 [User Parameter Default Value = Set defaults]
after setting parameters.
This saves parameter settings for a User Initialization.
The setting value for
o2-03
automatically goes back to
0
.
3. Any changes made after settings are saved as User Parameter Settings will be reset to the previously set value
when setting
A1-03 = 1110
.
The drive initializes parameter values by setting them back to the User Parameter Setting values.
2220 : 2-Wire Initialization
Resets MFDI terminal S1 to Forward Run and terminal S2 to Reverse Run, and resets all parameters to default
settings.
The drive will not initialize these parameters when
A1-03 = 2220
.
No.
Name
A1-00
Language Selection
A1-02
Control Method Selection
E1-03
V/f Pattern Selection
F6-08
Comm Parameter Reset @Initialize
F6-xx/F7-xx
Communication Option Parameters
Communication option card parameters are initialized when setting
F6-08 = 1 [Comm Parameter Reset @Initialize = Reset Back to
Factory Default]
.
L8-35
Installation Method Selection
o2-04
Drive Model (KVA) Selection
Note:
•
Setting
A1-06 [Application Preset]
automatically optimizes parameter settings for the application that was selected, although the drive
does not initialize
A1-02
when the user sets
A1-03 = 2220
.
•
Setting
A1-03 = 2220
initializes
A1-05 [Password Setting]
to
0000
. Be sure to set the password again for applications that require a
password.
■
A1-04: Password
No.
(Hex.)
Name
Description
Default
(Range)
A1-04
(0104)
Password
Enter the correct password set in
A1-05 [Password Setting]
to unlock parameters. You can view
parameter settings. Monitors are locked Enter the password in
A1-04 [Password]
to unlock and
change the settings.
0000
(0000 - 9999)
If the password entered in
A1-04
does not agree with the password setting in
A1-05
, you cannot change these
parameters:
•
A1-01 [Access Level Selection]
•
A1-02 [Control Method Selection]
•
A1-03 [Initialize Parameters]
•
A1-06 [Application Preset]
•
A2-01 to A2-32 [User Parameter 1 to 32]
To lock parameter settings after making changes without changing the password, enter the incorrect password in
A1-04
and push
.
Enter the Password to Unlock Parameters
Use this procedure to unlock parameter settings.
Set the password in
A1-05 [Password Setting]
, and show the Parameter Setting Mode screen on the keypad.
This procedure verifies the password, and makes sure that the parameter settings are unlocked.
1.
Push
or
to select “A: Initialization Parameters”, then push
.
2.
Push
or
to select
[A1-04]
, then push
.
You can now change parameter settings.
3.
Push
or
to move the digit and enter the password.
4.
Push
to confirm the password.
The drive unlocks the parameters and automatically shows the Parameters Screen.
V/f
CL-V/f
OLV
CLV
AOLV
Summary of Contents for CR700
Page 1: ......
Page 244: ...3 13 Test Run Checklist 244 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 422: ...7 7 Storage Guidelines 422 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 426: ...8 2 Disposal Instructions 426 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual ...
Page 837: ...EZZ023535 2 35 1 Revision History Revision Revised Content Date First Edition 2017 08 ...
Page 872: ...EZZ023536 2 16 Revision History Revision Revised Content Date First Edition 2017 08 ...