SCPI Commands for Digital Interfaces
TM-XDOP-01XN
4–29
Configure V, I, P Protection Limits
Over-Voltage Protection
To set the Over-Voltage Protection level:
SOUR:VOLT:PROT <voltage>
To check the Over-Voltage Protection level:
SOUR:VOLT:PROT?
To check if the Over-Voltage Protection was tripped:
SOUR:VOLT:PROT TRIP?
Alternatively, you can query the status registers. See Appendix B.
Under-Voltage Protection
To set the Under-Voltage Protection level:
SOUR:VOLT:PROT:UND <voltage>
SOUR:VOLT:PROT:UND:STAT <on-off-state>
The first UVP protection command sets the protection level. The second
command lets you choose a warning alarm only [OFF] or shut down with an alarm
[ON] if the protection level is exceeded.
To check the Under-Voltage Protection level:
SOUR:VOLT:PROT:UND?
To check if the Under-Voltage Protection was tripped:
SOUR:VOLT:PROT:UND:TRIP?
Alternatively, you can query the status register. See Appendix C, “SCPI
Command Reference”.
TM-XDOP-01XN.book Page 29 Monday, July 17, 2006 11:19 AM
Summary of Contents for XDC 10-1200
Page 2: ......
Page 3: ...XDC 6000 Watt and 12000 Watt Series Digital Programmable Power Supply Operating Manual ...
Page 8: ...vi ...
Page 12: ...x ...
Page 22: ...xx ...
Page 24: ...xxii ...
Page 48: ...Installation 2 10 TM XDOP 01XN Figure 2 5 Attaching the AC Input Wires for 6000 Watt units ...
Page 114: ...Operation 3 52 TM XDOP 01XN ...
Page 208: ...A 16 ...
Page 224: ...B 16 ...
Page 259: ...D Error Messages Appendix D lists all the error codes and their meanings ...
Page 268: ...D 10 ...
Page 283: ......