S
C
PI C
o
mmand S
u
mmary
TM-XDOP-01XN
C
–29
Table C-14
Auto Sequence Commands
Function
SCPI Command
Description
Query
Delete selected
sequence
[:]PROGram[<channel>][:SELected]:DELete[:SELect
ed]
The selected sequence is deleted
N/A
Delete all sequences
[:]PROGram[<channel>][:SELected]:DELete:ALL
All sequences are deleted
N/A
Select a sequence to
run or edit
[:]PROGram[<channel>][:SELected]:NAME
<sequence_number>
Select sequence to run or edit
Yes
Change Auto
Sequence operating
state
[:]PROGram[<channel>][:SELected]:STATe
{RUN|PAUSe|STOP}
Change operating state of current
auto sequence
Yes
Skip to the next step
(while running in
auto sequence)
[:]PROGram[<channel>][:SELected]:STEP:NEXT
Skip to start of next step. Error if
STATe is not RUN
N/A
Read selected
sequence number of
steps
[:]PROGram[<channel>][:SELected]:COUNt?
Read number of programmed
steps in selected sequence
Yes
Delete selected
sequence step
[:]PROGram[<channel>][:SELected]:STEP<step_numb
er>:DELete
Delete the selected sequence step
N/A
Exit a selected
sequence
[:]PROGram[<channel>][:SELected]:EXIT
Exit a selected sequence
N/A
Read current step
number
[:]PROGram[<channel>][:SELected]:STEP:EXECuting
?
Query current step in execution
N/A
Edit selected
sequence step
[:]PROGram[<channel>][:SELected]:STEP<step_numb
er>[:EDIT]
[[[[[<voltage>],<current>],<power>],<OVP_level>
],{<time>|TRIG}]
Edit the selected sequence step
Yes
Insert step into
selected sequence
[:]PROGram[<channel>][:SELected]:STEP<step_numb
er>:INSert
[[[[[<voltage>],<current>],<power>],<OVP_level>
],{<step_time|TRIG}]
Insert a step into the selected
sequence
N/A
Program selected
sequence step
current
[:]PROGram[<channel>][:SELected]:STEP<step_numb
er>:CURRent <current>
Edit/program step current of
selected sequence
Yes
TM-XDOP-01XN.book Page 29 Monday, July 17, 2006 11:19 AM
Summary of Contents for XDC 10-1200
Page 2: ......
Page 3: ...XDC 6000 Watt and 12000 Watt Series Digital Programmable Power Supply Operating Manual ...
Page 8: ...vi ...
Page 12: ...x ...
Page 22: ...xx ...
Page 24: ...xxii ...
Page 48: ...Installation 2 10 TM XDOP 01XN Figure 2 5 Attaching the AC Input Wires for 6000 Watt units ...
Page 114: ...Operation 3 52 TM XDOP 01XN ...
Page 208: ...A 16 ...
Page 224: ...B 16 ...
Page 259: ...D Error Messages Appendix D lists all the error codes and their meanings ...
Page 268: ...D 10 ...
Page 283: ......