Remote Analog Operation
TM-XDOP-01XN
4–5
Radiated
emissions
Add a ferrite block to the analog program lines and the user lines to reduce
radiated emissions. The 1-square inch ferrite block with built-in housing clip is
packaged and shipped with the power supply.
Position the block no more than 2” (50mm) from the power supply end of the
analog program and user lines.
The ferrite block is required for the power supply to meet radiated emissions
requirements for CE Mark approval.
J210 cable
Ferrite Block
To user interface
J210 connector
Max. 5 cm