Remote Operation
4–30
TM-XDOP-01XN
Over-Current Protection
T
o set the Over-Current Protection level:
SOUR:CURR:PROT <current>
SOUR:CURR:PROT:STAT <on-off-state>
The first OCP protection command sets the protection level. The second
command lets you choose a warning alarm only [OFF] or shut down with an alarm
[ON] if the protection level is exceeded.
To check the Over-Current Protection level:
SOUR:CURR:PROT?
To check if the Over-Current Protection was tripped:
SOUR:CURR:PROT:TRIP?
Under-Current Protection
To set the Under-Current Protection level:
SOUR:CURR:PROT:UND <current>
SOUR:CURR:PROT:UND:STAT <on-off-state>
The first UCP protection command sets the protection level. The second
command lets you choose a warning alarm only [OFF] or shut down with an alarm
[ON] if the protection level is exceeded.
To check the Under-Current Protection level:
SOUR:CURR:PROT?
To check if the Under-Current Protection was tripped:
SOUR:CURR:PROT:TRIP?