Electrical Specifications—Summary
TM-XDOP-01XN
A–5
Table A-4
Specifications for 12000 Watt units (80V to 600V Models)
Models
80–150
100–120
150–80
300–40
600–20
Output Ratings:
Output Voltage
a
Output Current
b
Output Power
a.
Minimum output voltage is <0.3% of rated voltage at zero output setting.
b.
Minimum output current is <0.2% of rated current at zero output setting when measured with rated load resistance.
0–80 V
0–150 A
12000 W
0–100 V
0–120 A
12000 W
0–150 V
0–80 A
12000 W
0–300 V
0–40 A
12000 W
0–600 V
0–20 A
12000 W
Line Regulation:
c
Voltage
(0.01% of Vmax)
Current (0.1% of Imax)
c.
For input voltage variation over the AC input voltage range, with constant rated load.
8 mV
150 mA
10 mV
120 mA
15 mV
80 mA
30 mV
40 mA
60 mV
20 mA
Load Regulation:
d
Voltage (0.05% of Vmax + 5 mV)
Current (0.2% of Imax + 40 mA)
d.
For 0–100% load variation, with constant nominal line voltage.
45 mV
340 mA
55 mV
280 mA
80 mV
200 mA
155 mV
120 mA
305 mV
80 mA
Meter Accuracy:
Voltage (0.15% of Vmax)
Current (0.5% of Imax)
120 mV
750 mA
150 mV
600 mA
225 mV
400 mA
450 mV
200 mA
900 mV
100 mA
Output Noise (0–20 MHz):
Voltage (p–p)
100 mV
100 mV
150 mV
250 mV
350 mV
Output Ripple (rms):
Voltage
Current
e
e.
Current mode noise is measured from 10% to 100% of rated output voltage, full current, unit in CC mode.
15 mV
640 mA
20 mV
460 mA
20 mV
240 mA
30 mV
100 mA
80 mV
50 mA
OVP Adjustment Range:
(0% to 103% of Vmax)
0–82.4 V
0–103 V
0–154.5 V 0–309 V
0–618 V
Efficiency:
f
f.
Typical efficiency at nominal input voltage and full output power.
0.89
0.90
0.90
0.91
0.91
Drift (30 minutes):
g
Voltage (0.04% of Vmax)
Current (0.6% of Imax)
g.
Maximum drift over 30 minutes with constant line, load, and temperature, after power on.
32 mV
900 mA
40 mV
720 mA
60 mV
480 mA
120 mV
240 mA
240 mV
120 mA
Drift (8 hours):
h
Voltage (0.02% of Vmax)
Current (0.05% of Imax)
i
h.
Maximum drift over 8 hours with constant line, load, and temperature, after 30 minute warm-up.
i.
Current drift for 600V-20A unit is 0.08% of Imax.
16 mV
75 mA
20 mV
60 mA
30 mV
40 mA
60 mV
20 mA
120 mV
16 mA
Temperature Coefficient:
j
Voltage (0.04% of Vmax/°C)
Current (0.06% of Imax/°C)
j.
Change in output per
°
C change in ambient temperature, with constant line and load.
32 mV
90 mA
40 mV
72 mA
60 mV
48 mA
120 mV
24 mA
240 mV
12 mA
TM-XDOP-01XN.book Page 5 Monday, July 17, 2006 11:19 AM
Summary of Contents for XDC 10-1200
Page 2: ......
Page 3: ...XDC 6000 Watt and 12000 Watt Series Digital Programmable Power Supply Operating Manual ...
Page 8: ...vi ...
Page 12: ...x ...
Page 22: ...xx ...
Page 24: ...xxii ...
Page 48: ...Installation 2 10 TM XDOP 01XN Figure 2 5 Attaching the AC Input Wires for 6000 Watt units ...
Page 114: ...Operation 3 52 TM XDOP 01XN ...
Page 208: ...A 16 ...
Page 224: ...B 16 ...
Page 259: ...D Error Messages Appendix D lists all the error codes and their meanings ...
Page 268: ...D 10 ...
Page 283: ......