background image

©2021, KEPCO, INC

1

Data subject to change without notice

228-1550 REV 17

 KEPCO, INC. 



 131-38 SANFORD AVENUE 



  FLUSHING, NY. 11355 U.S.A.



  TEL (718) 461-7000



 FAX (718) 767-1102

www.kepcopower.com   



 email: [email protected]

I N S T R U C T I O N   M A N U A L

KEPCO

An ISO 9001 Company.

HSF-PFC

150W SERIES

KEPCO SINGLE OUTPUT 150 WATT 

HOT SWAP PLUG-IN POWER SUPPLIES

I — INTRODUCTION

The Kepco HSF-PFC 150 Watt Series hot swappable, high
frequency switching, plug-in power supplies with built in
power factor correction employ forward conversion and are
designed to operate in a fault tolerant power system with
either a-c or d-c input. A negative temperature coefficient
(NTC) thermistor limits start-up surge. A built-in forced cur-
rent share circuit and OR-ing diodes allow configuration for
hot-swap and parallel-redundant N+1 operation. 

These power supplies are designed to be installed in
Kepco’s RA 19-(X)B Rack Adapters (Figure 2). RA 19-6B
accepts up to six 150W units, RA 19-7B accepts up to three
150W units, and up to four 50W or 100W units and RA 19-
8B accepts up to eight 50W or 100W units. The applicable
RA 19-(X)B Operator Manual can be downloaded from the
Kepco web site at:

   

www.kepcopower.com/support/opmanls.htm#ra19-xb

All input/output connections are through a 24 pin connector
that plugs in to the rack adapter. All external connections
are made through the rack adapter.

Seven models may be selected for outputs of 3.3, 5, 12, 15,
24, 28, or 48V (see Table 1 or 2).

When the input is cut off, the output is maintained for 20
milliseconds minimum. If the power supply shuts down due
to an output overvoltage condition, it is then necessary to
turn the unit off and wait 90 seconds minimum (120V a-c
input) or 120 seconds minimum (240V a-c input) before
turning the unit on again. 

Specifications for each model of the HSF-PFC 150 Watt
Series are listed in Section III, on page 4 (standard models)
and Section IV, on page 6 (suffix C, T, X and Y). 

OPTIONS.  

Options are identified by suffix: T (-PFCT)

offers improved efficiency and less weight; C (-PFCC):
offers current monitoring via an integral current sensing
resistor (includes option T); X (-PFCX) offers remote on/off
(includes option T); and Y (-PFCY) includes options C, X
and T.

II — FEATURES

FRONT PANEL ACCESS. 

 

The front panel provides a

power ON/OFF switch controlling input power and a “VDC
ON” light which indicates when the unit is operating. 

NOTE:

The ON/OFF switch must be set to OFF before remov-
ing unit from (or inserting into) rack adapter. 

The front panel “MASTER ON” LED lights when 1) the unit
operates independently, or 2) the unit is used in parallel
redundant configurations while a) the output current is
within 10% to 100% of nominal and the unit is functioning
as a master or b) the output current is less than 10% of
nominal. In parallel redundant configurations, the module
with the highest voltage functions as the master. The other
units are slaves, and track the output voltage of the master.
Refer to 

Current Share Bus (CSB)

 on page 3 for details.

(The MASTER ON LED is not used on 3.3V model; it is
always off.) 

The front panel Vadj trimmer provides adjustment of the
output voltage within the limits specified in Table 1 or 2; test
points connected to the +S and –S lines are available at the
front panel for measuring the output voltage.

FORCED CURRENT SHARE CIRCUIT.  

(Not avail-

able on 3.3V model.) When units are configured for N+1
parallel redundant operation, it is desirable for current to be
divided equally among the paralleled supplies. When the
CSB (Current Share Bus) lines of paralleled units are con-
nected together, the load current is forced to divide equally
between all paralleled units. If one unit fails, the remaining
units will continue to supply the load, and the load current
will be divided equally among the remaining operating
units. The failed unit is automatically isolated from the cir-
cuit by a built-in isolation diode. Refer to 

Current Share

Bus (CSB)

 on page 3 for details.

Summary of Contents for HSF 12-13PFC

Page 1: ...page 4 standard models and Section IV on page 6 suffix C T X and Y OPTIONS Options are identified by suffix T PFCT offers improved efficiency and less weight C PFCC offers current monitoring via an integral current sensing resistor includes option T X PFCX offers remote on off includes option T and Y PFCY includes options C X and T II FEATURES FRONT PANEL ACCESS The front panel provides a power ON...

Page 2: ...line ac input line failure etc results in an alarm All models include an isolated internal relay offering nor mally closed and normally open contacts referenced to an isolated common These contacts are rated for 1A at 30V d c and 0 5A at 125V a c These contacts may be used to configure close on failure or open on failure alarm cir cuits see Figure 3 for typical alarm circuits Refer to the applicab...

Page 3: ... each other and each unit must be operating at between 10 to 100 of rated output current If current to the load goes below 10 for each unit in cur rent share mode all MASTER ON lights may go on see load effect specifications this indicates that forced current share is no longer working units are simply in automatic current share mode If forced current sharing at less than 10 nominal current per su...

Page 4: ... 265V a c Load Effect 10 100 load change 0 5 typ 1 5 max except 3 3V model 1 typ 2 max Temperature Effect Range 10o to 71o C 0 5 typ 1 0 max Combined Effect includes source load and temperature effects 0 9 typ 1 8 max except 3 3V model 1 typ 2 max Time Effect 1 2 hr 8 hr at 25o C 0 2 typ 0 5 max TABLE 1 OUTPUT RATINGS AND SPECIFICATIONS HSF PFC 150W SERIES STANDARD NO SUFFIX MODEL HSF 3 3 30PFC HS...

Page 5: ...ient 10 to 85 relative humidity 100 Megohms min LEAKAGE CURRENT Per IEC 950 and UL 1950 0 23 mA typ 0 35 mA max 120V a c 60Hz 0 45 mA typ 0 7 mA max 240V a c 60Hz SAFETY All units designed to meet EN 60950 U S UL 60950 3rd Ed Canada CAN CSA 22 2 No 60950 00 3rd Ed ambient temp 50 C 150W units are CE marked per the Low Voltage Directive LVD EN60950 The standards do not apply with DC input operation...

Page 6: ...2 PFCC PFCT PFCX PFCY HSF 15 10 PFCC PFCT PFCX PFCY HSF 24 6 3 PFCC PFCT PFCX PFCY HSF 28 5 3 PFCC PFCT PFCX PFCY HSF48 3 1 PFCC PFCT PFCX PFCY OUTPUT VOLTS d c NOMINAL 3 3V 5V 12V 15V 24V 28V 48V ADJUSTMENT RANGE 2 8 3 4V 4 3 5 3V 9 8 13 0V 12 8 16 3V 19 2 26 0V 23 0 30 2V 40 0 52 2 OVERVOLTAGE SETTING 1 2 3 4 4 6V 5 2 6 5V 13 2 15 2V 16 8 18 8V 26 5 30 3V 31 5 34 8V 54 5 59 8V OUTPUT CURRENT NOM...

Page 7: ...00V a c for one minute Between input and case ground 2KV a c for one minute INSULATION RESISTANCE Between input and ground output and ground input and output 500V d c 15 to 35 C ambient 10 to 85 relative humidity 100 Megohms min LEAKAGE CURRENT Per IEC 950 and UL 1950 0 29 mA typ 0 45 mA max 120V a c 60Hz 0 40 mA typ 0 65 mA max 240V a c 60Hz SAFETY All units designed to meet EN 60950 2001 U S UL ...

Page 8: ...o fault When output voltage is available the green VDC ON LED is on While monitoring output voltage at the front panel test points the Output Voltage Adjust trimmer allows adjustment of the output voltage FIGURE 5 COMPONENT LOCATIONS Master slave parallel configurations of one or more power supplies are covered in the applicable RA 19 X B Rack Adapter manual The MASTER ON LED amber goes on under a...

Page 9: ...ANFORD AVENUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 www kepcopower com email hq kepcopower com 081721 228 1550 REV 17 9 FIGURE 6 HSF PFC 150W INCLUDING SUFFIX C T X AND Y POWER SUPPLY OUTLINE DRAWING ...

Reviews: