Explanation of Function
Seite 66 / 180
Output Frequency Start/End
External analog signal from the control terminals
(frequency command)
O-L terminal : 0 - 10V
OI-L terminal : 4 - 20mA
O2-L terminal : -10 - 10V
Set output frequency for one of the above
(1)Start, End of O-L terminal, OI-L terminal
Set item
Function
code
Data Contents
O/OI start
A011/A101
0.00-400.0 Unit : Hz Set starting frequency
O/OI end
A012/A102
0.00-400.0 Unit : Hz Set ending frequency
O/OI start rate
A013/A103
0.-100.
Unit : %
Set start rate for output frequency command 0-10V,
4-20mA
O/OI end rate
A014/A104
0.-100.
Unit : %
Set end rate for output frequency command 0-10V,
4-20mA
00
External start frequency
Output frequency from 0 to A013/A103 outputs the value
of A011/A101
O/OI start
Selection
A015/A105
01
0Hz
Output frequency from 0 to A013/A103 outputs the value
of 0Hz
When the input is from 0 to 5V with O-L terminal, set A014 to 50%.
(Example 1) A015/A105 : 00 (Example 2) A015/A105 : 01
Frequency
command
Maximum
frequency
A012/A102
A011/A101
0 A013/A103 A014/A104 100%
(0V/4mA) (10V/20mA)
Frequency
command
Maximum
frequency
A012/A102
A011/A101
0 A013/A103
A014/A104 100%
(0V/4mA) (10V/20mA)